Plan Review Notes For Permit 07070744 |
Permit Number |
07070744 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-05 07:05:06 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | FS, RESPECTIVELY. | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES | | APPLY. | | | | AN ELECTRICAL LOCK CHANGE IS IN THE DESCRIPTION ON THE | | APPLICATION. IF THE CIRCUIT FOR THAT LOCK IS EXTENDED | | AN ELECTRICAL PERMIT IS REQUIRED PER 105 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|