Plan Review Notes For Permit 07070744 |
Permit Number |
07070744 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-29 10:37:29 | COMMERCIAL SCREEN ENCLOSURE BUILDING REVIEW FIRST | | CHECKLIST. | | REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- PROVIDE COMPLETE ENGINEERED DRAWINGSAS REQUIRED BY | | SEC. 2002.1 FBC 2004. | | PLEASE MAKE SURE ENGINEER SIGNING AND SEALING DRAWINGS | | PROVIDES ALL HIS INFORMATION AS REQUIRED BY SEC. | | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE AND CHAPTER | | 471 FLORIDA STATUTES. | | | | 2- CLEARLY IDENTIFY WHAT'S NEW AND WHAT'S EXISTING. | | CLARIFY IF CHANGING DOOR SIZES OR NUMBER OF DOORS. NEED | | TO VERIFY THAT EGRESS REQUIREMENTS ARE NOT CHANGED. | | SPECIFY ON PLANS. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | 2004. | | | | 3- PLANS TO SPECIFY ALL WIND DESIGN DATA THAT APPLIES | | TO THIS JOB AS REQUIRED BY SEC. 1603.1.4 FBC 2004. | | ALSO,SPECIFYCODE BY WHICH STRUCTURE IS DESIGNED. | | FBC 2004. | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|