2007-08-29 10:37:29COMMERCIAL SCREEN ENCLOSURE BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE COMPLETE ENGINEERED DRAWINGSAS REQUIRED BY
 SEC. 2002.1 FBC 2004.
 PLEASE MAKE SURE ENGINEER SIGNING AND SEALING DRAWINGS
 PROVIDES ALL HIS INFORMATION AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 471 FLORIDA STATUTES.
  
 2- CLEARLY IDENTIFY WHAT'S NEW AND WHAT'S EXISTING.
 CLARIFY IF CHANGING DOOR SIZES OR NUMBER OF DOORS. NEED
 TO VERIFY THAT EGRESS REQUIREMENTS ARE NOT CHANGED.
 SPECIFY ON PLANS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 3- PLANS TO SPECIFY ALL WIND DESIGN DATA THAT APPLIES
 TO THIS JOB AS REQUIRED BY SEC. 1603.1.4 FBC 2004.
 ALSO,SPECIFYCODE BY WHICH STRUCTURE IS DESIGNED.
 FBC 2004.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.