Plan Review Notes
Plan Review Notes For Permit 07070735
Permit Number 07070735
Review Stop G
Sequence Number 1
Notes
Date Text
2007-08-08 14:05:03DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE CORRESPONDING LENGTHS NEED TO BE INDICATED
 FOR THE CUT LENGTHS OF PIPE ON THE ISOMETRIC TO VERIFY
 THE INDICATED LONGEST LENGTH OF EIGHTY FEET (80') ON
 THE RESUBMITTAL.
  
 2. PLEASE NOTE THE RED LINE CORRECTIONS TO THE CSST
 PER TABLE 402.4(14) AND THE GALV. DROP TO THE STOVE PER
 TABLE 402.4(2) AND CORRECT THESE ERRORS ON THE
 RESUBMITTAL. PLEASE REFERENCE THE ATTACHED TABLES TO
 THE DENIED GAS COMMENTS INDICATING THESE CORRECTIONS.
  
 3. PLEASE NOTE THAT THERE ARE TWO POEPLE TAKING
 RESPONSIBILITY FOR THE DESIGN OF THE DRAWING BY
 PRINTING, SIGNING AND DATING THE DRAWING. PER FBC-2004
 CHAPTER 1, SECTION 106.3.4.3 ONLY ONE PERSON NEEDS TO
 BE RESONSIBLE FOR THE DESIGN OF THE DRAWING. PLEASE
 DELETE ONE OF THE SIGNATURES ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED AND
 PROVIDE ONE COPY OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  