2007-08-24 13:46:01 | BUILDING PLAN REVIEW |
| PERMIT: 07070734 |
| ADD: 480 HIBISCUS ST |
| CONT: LATITE ROOFING |
| TEL: (954)275-6024 |
| BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) 2ND REVIEW, ALL PRODUCT APPROVALS ARE TO BE REVIEWED |
| BY THE DESIGN PROFESSIONAL, THESTRUCTURAL ENGINEER |
| DEL LOS REYES, THE STRUCTURAL ENGINEER DOESN'T HAVE |
| THEIR SHOP DRAWING STAMP INDICATING THEIR REVIEW WITH |
| APPROVAL;WPB ADMIN CODE 106.3* PRODUCT APPROVALS. |
| THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 4) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER RULE 9B-72. SEE |
| WWW.FLORIDABUILDING.ORG |
| |
| 5) SHEET S-8.4 IS A MINIATURIZED COPY BUT STILL |
| REQUIRES THE ENGINEER OF RECORD TO SIGN AND SEAL SHEET. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| |
| 6) THE FLAT ROOF NOA SUBMITTED 06-0626.05 WILL REQUIRE |
| ENHANCED FASTENING WILL BE REQUIRED FOR ZONE# 3 IF TWO |
| OR THREE ROWS ARE INSTALLED. PLEASE SUBMIT RAS 117 |
| CALCULATION. |
| NOTE BUILDING HEIGHT OF 119?-0? PLUS AN IMPORTANCE |
| FACTOR OF 1.15 SEE STRUCTURAL SHEET S1.0. ) JOHN |
| MANSVILLE REPORT NOA (06-0626.05) INDICATE LOW |
| PRESSURES OF -75 PSF, WILL REQUIRE ENHANCED FASTENING |
| SEE LIMITATION# 7 ; |
| XX___ THE SYSTEM PROVIDED STATESLIMITATION# 7, |
| CALCULATIONS FROM RAS 117 SHALL BE SUBMITTED,THE |
| FASTENERRESISTANCE BE LESS THAN THATREQUIRED, AS |
| DETERMINED BY THEBUILDING OFFICIAL, A REVISED |
| FASTENER SPACING, PREPARED , SIGNED AND SEALED BY A |
| FLORIDA REGISTEREDPROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| SUBMITTED. |
| |
| 7)THE SHOP DRAWINGS SUBMITTED BY LATITE ROOFING HAVE |
| NEVER BEEN REVIEWED BY THE DESIGN PROFESSIONALS. WPB |
| ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT |
| WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 8) THE METAL ROOF SYSTEM SUBMITTED FIRESTONE METAL |
| PRODUCTS NOA 06-0821.10 HAS A MAXIMUM DESIGN PRESSURE |
| OF-71.0 PSF FIELD |
| |
| -101.0 PSF PERIMETERS AND CORNERS |
| SHEET 5 OF THE NOA INDICATES THE PANELS TO BE 16" WIDE |
| OR 1.33 SQ FT. |
| THE PLANS CLEARLY INDICATE A -75 PSF IN THE FIELD X |
| 1.33 A RUNNING FOOT= 99.75 POUNDS PER RUNNING FOOT. |
| SYSTEMS LIMITATION # 1 DOES NOT ALLOW FOR ENHANCEMENT. |
| FOR THE CORNER OR END ZONES THE PLANS INDICATE A -85 |
| PSF X 1.33 A RUNNING FOOT=113.05, AGAIN THE SYSTEM |
| LIMITATION OF -101.0 NO ENHANCED FASTENING IS ALLOWED. |
| ALL PRODUCT APPROVALS ARE TO BE REVIEWED BY THE DESIGN |
| PROFESSIONAL, THESTRUCTURAL ENGINEER DEL LOS REYES, |
| THE STRUCTURAL ENGINEER DOESN'T HAVE THEIR SHOP DRAWING |
| STAMP INDICATING THEIR REVIEW WITH APPROVAL;WPB ADMIN |
| CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| |
| BUILDING PLAN REVIEW II |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |