Plan Review Notes For Permit 07070713 |
Permit Number |
07070713 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-22 08:02:11 | SIGNBUILDING REVIEWFIRST CHECKLIST. | | REVIEW DONE UNDER FBC 2004 WITH 2006/2007 REVISIONS. | | | | 1- THERE IS NOT ENOUGH STRUCTURAL INFORMATION SHOWING | | HOW THE SIGN IS GOING TO BE ATTACHED TO STRUCTURE TO | | RESIST THE 150MPH WIND LOAD.THE ONLY STRUCTURAL | | SPECIFICATION SHOWN ON DRAWING IS: "MIN. 3/8 X 3 | | EXPANSION ANCHORS".THERE ARE NOT ENOUGH | | SPECIFICATIONS FOR HOW MANY ANCHORS ARE REQUIRED TO | | WITHSTAND THE 150MPH WIND LOAD.SPECIFY ANCHOR | | SPACING, ETC. PROVIDE COMPLETE INFORMATION.SEC. | | 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | SEC. 713.13 FLORIDA STATUTE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|