Plan Review Notes For Permit 07070688 |
Permit Number |
07070688 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-23 16:06:18 | BUILDING REVIEW CHECKLIST: | | 1- PERMIT APPLICATION NEEDSTO SPECIFY BUILDING MEAN | | ROOF HEIGHT AS REQUIRED BY CITY POLICY FOR ROOFING | | PERMITS TO VERIFY COMPLIANCE WITH UPLIFT PRESSURES OF | | SEC. 1609FBC 2004.SEE ATTACHED COPY OF CITY | | POLICY. | | | | | | 2- NEED TO SPECIFY THE SPECIFIC APPROVED ASSEMBLYTO | | BE INSTALLED.SUBMIT ONLY THE APPROVED ASSEMBLYTO BE | | INSTALLED ALONG WITH THE REST OF THE PRODUCT APPROVAL | | INFORMATION. DON'T SUBMIT THE REST OF THE APPROVED | | ASSEMBLIES. SEE ATTACHED COPY OF CITY POLICY. | | | | 3- ON SELECTED APPROVED ASSEMBLYINDICATE WHICH | | SPECIFIC FASTENING OPTION IS GOING TO BE USED AS | | REQUIRED BY CITY POLICY FOR RE-ROOFING PERMITS. | | | | 4- IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #7, THEN PROVIDE THE RAS 117 CALCULATIONS | | FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS TO | | MEET THE UPLIFT PRESSURES OF TABLE 1609.6.2.1(2) OF FBC | | 2004. | | *** IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #9, THEN IT CAN BE USED IN THIS AREA BECAUSE | | GENERAL LIMITATION #9DOESN'T ALLOW NAIL ENHANCING. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (5610805-6712 |
|