Plan Review Notes
Plan Review Notes For Permit 07070665
Permit Number 07070665
Review Stop P
Sequence Number 5
Notes
Date Text
2008-01-29 13:54:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2006 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 1. SHEET 1, SANITARY PLUMBING RISER DIAGRAM: THE
 BATHROOM GROUP IS NOT VENTED. PER FBC PLUMBING SECTION
 *909.1 WET VENT PERMITTED.
  
 2. SHEET 1, SANITARY PLUMBING RISER DIAGRAM: THE
 SHOWER NEEDS A WATER-SEAL TRAP. PER FBC PLUMBING
 SECTION *1002.1 FIXTURE TRAPS.
  
 3.ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH
 REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION
 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  