2008-01-24 17:04:04 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE REVISIONSUBMITTED NOW HAS A TANKLESS ELECTRIC
 WATER HEATER WITH OCP IN A CLOTHES CLOSET IN VIOLATION
 OF 240.24(D). REMOVE FROM CLOSET.
  
 2} THE LOAD CALCULATIONWAS NOT REVISED TO INDICATE THE
 NEW LOAD, REVISE SAME PER ARTICLE 220.
  
 3} SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS, THAT INCLUDE THE ELECTRICAL
 SPECIFICATIONS, FOR THE WATER HEATER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  