Plan Review Notes For Permit 07070665 |
Permit Number |
07070665 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-11-02 12:58:41 | RESIDENTIAL REPAIRS BUILDING REVIEWPROVISO: | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | 9B-72 FOR:ALL SIMPSON CONNECTORS SPECIFIED ON | | DRAWINGS BY THE ENGINEER OF RECORD. | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | PRODUCT APPROVAL REQUESTED ON ITEM 1 ABOVE AS REQUIRED | | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | 3- ENGINEER TO SPECIFY BUILDING CONSTRUCTION TYPE AS | | REQUIRED BY 602.1 FBC 2004.NEED TO IDENTIFY IF | | CONSTRUCTION TYPE A OR B. SEE SEC. 602.1 FBC 2004. | | | | 4- TYPICAL WALL SECTION: | | A) WHERE WAS CONNECTOR MSTM16 TAKEN FROM? LOOKED IN | | 2007 SIMPSON CATALOG AND WAS UNABLE TO FIND IT TO | | VERIFY COMPLIANCE WITH PROPOSED APPLICATION. NEED A | | WOOD TO MASONRY CONNECTOR.***NOTE: KEEP IN MIND THAT | | WHEN TYPE AND NUMBER OF FASTENERS ARE DIFFERENT FROM | | THOSE TESTED AND PUBLISHED BY THE MANUFACTURER, THEN | | COMPLETE ENGINEERING ANALYSIS WILL BE REQUIRED TO SHOW | | HOW THE LOADSARE ACHIEVED. SEC. 106.1.2 CITY | | AMENDMENTS TO FBC 2004. | | | | B) ENGINEER OF RECORD NEEDS TO REVIEW PRODUCT | | APPROVALFOR HARDIPANEL SIDING AND REVISE WALL | | SHEATHING SIZE TO MATCH SIZE REQUIRED ON THE PRODUCT | | APPROVAL. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|