2007-10-03 18:04:14 | RESIDENTIAL REPAIRS BUILDING REVIEW SECOND CHECKLIST. |
| REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND |
| 2004 FBC EXISTING BUILDINGWITH 2007 REVISIONS. |
| |
| 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: |
| A) NEW SINGLE HUNG WINDOWS. INFORMATION SUBMITTED IS |
| NOT AN APPROVED PRODUCT APPROVAL. VISIT |
| WWW.FLORIDABUILDING.ORG TO DOWNLOAD APPROVED FLORIDA |
| PRODUCT APPROVALS.OR PROVIDE DADE COUNTY NOA. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS AND DETAILS.REPEAT COMMENT, NOT ADDRESSED. |
| |
| 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 3- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1 |
| FBC 2004 AND SEC. 106.1.2CITY AMENDMENTS TO FBC 2004. |
| REPEATED COMMENT, NOT ADDRESSED. |
| |
| 4- TYPICAL WALL SECTION; |
| A) PROVIDE COMPLETE TYPICAL WALL SECTION SHOWING |
| CONNECTORS ON TOP AND BOTTOM OF WOOD STUDS. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. SECTION/DETAIL |
| SHOWN IS INCOMPLETE. REPEAT COMMENT, NOT ADDRESSED. |
| |
| B) NEED TO REVISE SIMPSON TS18 CONNECTOR. THIS IS A |
| WOOD TO WOOD CONNECTOR. NEED TO SPECIFY WOOD TO MASONRY |
| CONNECTOR. SEE CATALOG AND REVISE AS REQUIRED. REPEAT |
| COMMENT, NOT PROPERLY ADDRESSED. |
| |
| 5- NOTICE OF COMMENCEMENT WAS RECORDED ON 5/16/2007. IT |
| EXPIRES AFTER 90 DAYS OF RECORDING IF WORK IS NOT |
| STARTED. SEC. 713.13 FLORIDA STATUTE.NEED TO PROVIDE |
| RE-RECORDED NOTICE OF COMMENCEMENT. |
| |
| 6- PLEASE DON'T STAPLE PRODUCT APPROVALS TO DRAWINGS. |
| THIS WILL HELP EXPEDITE THE REVIEW PROCESS. |
| |
| 7- DRAWING 2 OF 2 IS NOT LEGIBLE. IS THIS DRAWING |
| REALLY REQUIRED.COORDINATE INFORMATION IN THIS |
| DRAWING WITHHARDIPLANK PRODUCT APPROVALTO AVOID |
| CONFLICTS AND DELAYS IN THE REVIEW PROCESS. |
| |
| 8- SEE ZONING COMMENTS. |
| |