2007-08-10 15:02:24 | SIGN BUILDING REVIEW FIRSTCHECKLIST. |
| REVIEW UNDER FBC 2004. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| 2- ENGINEERED DRAWING SHEET #1 IS MISSING THE |
| DIMENSIONS FOR THE SIGN.ENGINEERED DRAWINGS TO HAVE |
| ALL THE INFORMATION INCLUDING SIGN DIMENSIONS. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 3- ACCORDING TOSECTION THRU CABINET DETAIL ON SHEET |
| #1, THESIGN IS TO HAVE (3) 3/8" X 1-1/2" SLEEVE |
| ANCHORS.PROVIDE ENGINEERING CALCULATIONS SHOWING HOW |
| ONLY THREE ANCHORS ARE ADEQUATE TO RESIST THE WIND |
| LOADS SPECIFIEDON ITEM #9 OF DESIGN, FABRICATION AND |
| CONSTRUCTION NOTES ON SHEET # 1AND THE SIZE OF THE |
| SIGN. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 4-"HEART OF THE SYSTEM"DETAIL SHOWN ON SHEET #1 |
| STATES THAT STAINLESS OR GALVANIZED STAPLESHOLD |
| SECURELY IN WINDS UP TO 110MPH.NEED TO PROVIDE DESIGN |
| THAT HOLDS FOR AT LEAST 148MPH AS SPECIFIED ON ITEM #9 |
| OF THE DESIGN, FABRICATION AND CONSTRUCTION NOTES ON |
| SHEET #1. |
| |
| 5- ENGINEER'S SEAL HAS THE WRONG NUMBER IMPRESSED ON |
| THE SEAL.CORRECT ENGINEER LICENSE NUMBER IS 26818, |
| NOT 20818. REVISE SEAL AS REQUIRED. |
| |
| 6- ENGINEER TO PROVIDE HIS LICENSE NUMBER IN ALL SHEETS |
| AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND SEC. |
| 61G15-23.002 OF CITY ADMINISTRATIVE CODE.LOOK ON |
| WEBSITE FOR FOR THIS SECTIONS AND PROVIDE ALL |
| INFORMATION AS REQUIRED. |
| |
| 7- UPDATE ALL REFERENCE STANDARDS AND YEAR AS ADOPTED |
| BY FBC 2004.SEE CHAPTER 35 OF FBC 2004 AND REVISE |
| ALL SPECIFIED STANDARDS AND EDITIONSSPECIFIED ON |
| SHEET #1 AS REQUIRED. |
| |