Plan Review Notes
Plan Review Notes For Permit 07070617
Permit Number 07070617
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-10 15:02:24SIGN BUILDING REVIEW FIRSTCHECKLIST.
 REVIEW UNDER FBC 2004.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- ENGINEERED DRAWING SHEET #1 IS MISSING THE
 DIMENSIONS FOR THE SIGN.ENGINEERED DRAWINGS TO HAVE
 ALL THE INFORMATION INCLUDING SIGN DIMENSIONS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- ACCORDING TOSECTION THRU CABINET DETAIL ON SHEET
 #1, THESIGN IS TO HAVE (3) 3/8" X 1-1/2" SLEEVE
 ANCHORS.PROVIDE ENGINEERING CALCULATIONS SHOWING HOW
 ONLY THREE ANCHORS ARE ADEQUATE TO RESIST THE WIND
 LOADS SPECIFIEDON ITEM #9 OF DESIGN, FABRICATION AND
 CONSTRUCTION NOTES ON SHEET # 1AND THE SIZE OF THE
 SIGN. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 4-"HEART OF THE SYSTEM"DETAIL SHOWN ON SHEET #1
 STATES THAT STAINLESS OR GALVANIZED STAPLESHOLD
 SECURELY IN WINDS UP TO 110MPH.NEED TO PROVIDE DESIGN
 THAT HOLDS FOR AT LEAST 148MPH AS SPECIFIED ON ITEM #9
 OF THE DESIGN, FABRICATION AND CONSTRUCTION NOTES ON
 SHEET #1.
  
 5- ENGINEER'S SEAL HAS THE WRONG NUMBER IMPRESSED ON
 THE SEAL.CORRECT ENGINEER LICENSE NUMBER IS 26818,
 NOT 20818. REVISE SEAL AS REQUIRED.
  
 6- ENGINEER TO PROVIDE HIS LICENSE NUMBER IN ALL SHEETS
 AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND SEC.
 61G15-23.002 OF CITY ADMINISTRATIVE CODE.LOOK ON
 WEBSITE FOR FOR THIS SECTIONS AND PROVIDE ALL
 INFORMATION AS REQUIRED.
  
 7- UPDATE ALL REFERENCE STANDARDS AND YEAR AS ADOPTED
 BY FBC 2004.SEE CHAPTER 35 OF FBC 2004 AND REVISE
 ALL SPECIFIED STANDARDS AND EDITIONSSPECIFIED ON
 SHEET #1 AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712