2007-08-26 14:17:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE OPENING 2.YOU STATE THAT YOU ARE DESIGNING
 TO -77PSF, BUT 47.2 REQUIRES 6" SPACING FOR PANELS, C2
 CONNECTION, 2" EDGE DISTANCE (7" FOR 3" EDGE DISTANCE).
 SPECIFY EDGE DISTANCE AND REVISE ANCHOR SPACING.
  
 2.)OPENING 1, ACCORDION, STATES ANCHOR SPACING IS 4"
 BUT ON SHEET 7 YOU'VE WRITTEN "DRILLED EVERY 10
 INCHES".4" IS REQUIRED.PLEASE REMOVE THE NOTE OR
 CLARIFY AS TO WHAT THIS MEANS.
  
  