Plan Review Notes For Permit 07070593 |
Permit Number |
07070593 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-08-26 14:17:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)SEE OPENING 2.YOU STATE THAT YOU ARE DESIGNING | | TO -77PSF, BUT 47.2 REQUIRES 6" SPACING FOR PANELS, C2 | | CONNECTION, 2" EDGE DISTANCE (7" FOR 3" EDGE DISTANCE). | | SPECIFY EDGE DISTANCE AND REVISE ANCHOR SPACING. | | | | 2.)OPENING 1, ACCORDION, STATES ANCHOR SPACING IS 4" | | BUT ON SHEET 7 YOU'VE WRITTEN "DRILLED EVERY 10 | | INCHES".4" IS REQUIRED.PLEASE REMOVE THE NOTE OR | | CLARIFY AS TO WHAT THIS MEANS. | | | | |
|