Date |
Text |
2007-08-06 10:02:46 | DENIED |
| REFERENCE: |
| ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS. |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PLEASE CORRELATE THE SPA SPECIFICATIONS WITH THE |
| SPA PLANS ON THE RESUBMITTAL. SPA SPECIFICATIONS ARE |
| INDICATING 7 THERAPY JETS AND THE SPA PLANIS |
| INDICATING 6 THERAPY JETS. |
| |
| 2. FBC-2004 SEC. 424.2.6.6.5, OR |
| FBCR-2004 SEC. R4101.6.6.5 WHERE |
| PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| FITTING SHALL BE LOCATED AT LEAST 6" AND |
| NOT GREATER THAN 12" BELOW THE MINIMUM |
| OPERATING WATER LEVEL OR AS AN |
| ATTACHMENT TO THE SKIMMER. |
| NOTE: DETAIL REQUIRED WITH MAKE AND MODEL NUMBER OF THE |
| FITTING. |
| |
| 3. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| R4101.9 WATER SUPPLY, LOCAL ORD. |
| #2853-95, BACKFLOW REQUIRED ON WATER |
| SERVICE.(PLEASE ADD TO NOTES ON THE RESUBMITTAL) |
| |
| 4. FBC-2004 SEC. 424.2.12.1, OR |
| FBCR-2004 SEC. R4101.12.1 PRESSURE |
| TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| NO AIR TEST SHALL BE APPROVED FOR PVC |
| PIPE AND FITTINGS. (PLEASE ADD TO NOTES ON THE |
| RESUBMITTAL) |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL= [email protected] |
| |
| |