Plan Review Notes
Plan Review Notes For Permit 07070573
Permit Number 07070573
Review Stop P
Sequence Number 1
Notes
Date Text
2007-08-06 10:02:46DENIED
 REFERENCE:
 ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS.
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE CORRELATE THE SPA SPECIFICATIONS WITH THE
 SPA PLANS ON THE RESUBMITTAL. SPA SPECIFICATIONS ARE
 INDICATING 7 THERAPY JETS AND THE SPA PLANIS
 INDICATING 6 THERAPY JETS.
  
 2. FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: DETAIL REQUIRED WITH MAKE AND MODEL NUMBER OF THE
 FITTING.
  
 3. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(PLEASE ADD TO NOTES ON THE RESUBMITTAL)
  
 4. FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (PLEASE ADD TO NOTES ON THE
 RESUBMITTAL)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved