Plan Review Notes For Permit 07070573 |
Permit Number |
07070573 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-26 10:23:41 | | | | | DENIED/INCORRECT INFORMATION | | | | THE BONDING GRID NOTE ON THE LAST (UNTITLED) SHEET OF | | THE PLAN INCORRECTLY STATES THAT THE" #8 BONDING WIRE | | IS TO BE PLACED AROUND THE PERIMETER 36" FROM THE POOL | | WATERS EDGE-----".THE TEXT OF SB 2836 READS "18 INCHES | | TO 24" FROM INSIDE THE WALL OF A SWIMMING POOL OR SPA" | | PLEASE CORRECT THAT NOTE TO INSURE THE INTENT IS MET | | AND AVOID CONFUSION IN THE FIELD. | | | | NOTE: I HAVE ATTACHED A COPY OF SENATE BILL 2836, AS IT | | PERTAINS TO ARTICLE 680, FOR THE POOL CONTRACTOR AND | | FOR THE ENGINEER, FOR YOUR RECORDS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|