Plan Review Notes
Plan Review Notes For Permit 07070573
Permit Number 07070573
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-26 10:23:41 
  
 DENIED/INCORRECT INFORMATION
  
 THE BONDING GRID NOTE ON THE LAST (UNTITLED) SHEET OF
 THE PLAN INCORRECTLY STATES THAT THE" #8 BONDING WIRE
 IS TO BE PLACED AROUND THE PERIMETER 36" FROM THE POOL
 WATERS EDGE-----".THE TEXT OF SB 2836 READS "18 INCHES
 TO 24" FROM INSIDE THE WALL OF A SWIMMING POOL OR SPA"
 PLEASE CORRECT THAT NOTE TO INSURE THE INTENT IS MET
 AND AVOID CONFUSION IN THE FIELD.
  
 NOTE: I HAVE ATTACHED A COPY OF SENATE BILL 2836, AS IT
 PERTAINS TO ARTICLE 680, FOR THE POOL CONTRACTOR AND
 FOR THE ENGINEER, FOR YOUR RECORDS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER