Plan Review Notes For Permit 07070568 |
Permit Number |
07070568 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-07 14:06:06 | *****DENIED***** | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.THE REMOVAL AND/OR THE REPLACEMENT OF BUILDING | | MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER | | ACCESS TO OR EGRESS FROM THE 5TH FLOOR CORRIDOR OR ANY | | OTHER FLOOR IN THE BUILDING. | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE | | PROPOSED WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS | | C. | | | | 6.DOORS SHALL BE NOT LESS THAN 78 INCHES IN NOMINAL | | HEIGHT.PLEASE EXPLAIN/CLARIFY DIMENSION OF THE | | PROPOSED CLOSET DOORS. | | | | 7.PLEASE INDICATE IF THE UNIT SPACE'S SMOKE DETECTION | | DEVICES ARE ACTUALLY SMOKE DETECTORS OR SMOKE ALARMS. | | PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE TIED | | INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS SMOKE | | ALARMS (SA) ALERT THE OCCUPANT(S) OF THE UNIT SPACE | | ONLY. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS | | ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|