Plan Review Notes
Plan Review Notes For Permit 07070568
Permit Number 07070568
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-08-07 14:06:06*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE REMOVAL AND/OR THE REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER
 ACCESS TO OR EGRESS FROM THE 5TH FLOOR CORRIDOR OR ANY
 OTHER FLOOR IN THE BUILDING.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE
 PROPOSED WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
 6.DOORS SHALL BE NOT LESS THAN 78 INCHES IN NOMINAL
 HEIGHT.PLEASE EXPLAIN/CLARIFY DIMENSION OF THE
 PROPOSED CLOSET DOORS.
  
 7.PLEASE INDICATE IF THE UNIT SPACE'S SMOKE DETECTION
 DEVICES ARE ACTUALLY SMOKE DETECTORS OR SMOKE ALARMS.
 PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE TIED
 INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS SMOKE
 ALARMS (SA) ALERT THE OCCUPANT(S) OF THE UNIT SPACE
 ONLY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW