Plan Review Notes
Plan Review Notes For Permit 07070568
Permit Number 07070568
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-03 14:24:49 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT.
  
 1} PROVIDE A PANEL SCHEDULE SO THAT OVERCURRENT
 PROTECTION AND WIRE SIZES PER 310.16 CAN BE REVIEW, AND
 REQUIRED CIRCUITS PER 210.11 CAN BE VERIFIED AS
 COMPLIANT
  
 2} THE ISLAND RECEPTACLE(S) MUST COMPLY WITH
 210.52(C)(2). THE RECEPTACLE 16" FROM THE FLOOR WILL
 NOT MEET THE REQUIREMENT, ALSO GFCI IS REQUIRED PER
 210.8(A)(6).
  
 3} A SMOKE ALARM NEEDS TO BE ADDED OUTSIDE THE MASTER
 BEDROOM TO MEET THE INTENT OF R313.1.1" OUTSIDE EACH
 SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS"
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE PUT A ON
 THE PLAN FOR CLARITY IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]