Date |
Text |
2007-07-23 07:41:05 | |
| |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} } PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. |
| |
| 2} INDICATE HOW THE MAIN HOUSE IS BEING FED. THE PLAN |
| SHOWS ONLY ONE PANEL LOCATION. PLEASE LOCATE ALL |
| SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, |
| DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH |
| ARTICLES 225 AND 230 CAN BE REVIEWED. |
| |
| 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| PROTECTED PER 210.8(A) (1). INDICATE SAME ON THE PLAN. |
| |
| 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| 106.3.4.3.FBC. |
| |
| 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| SHALL BE INTERCONNECTED AND HARD WIRED INDICATE |
| LOCATIONS AND INTENT ON THE PLAN. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |