Date |
Text |
2007-08-13 16:14:43 | 2004 FBC W/2007 REVISIONS |
| INSTALL PANEL WALLS AND SLAB |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE PERMIT APPLICATION SPECIFIES A NEW STRUCTURAL |
| ROOF AND THE PLANS SPECIFY THE ROOF AS EXISTING. PLEASE |
| CLARIFY. |
| |
| 3) THE SIGNED AND SEALED DRAWINGS ARE REQUIRED TO HAVE |
| THE ORIGINAL SIGNATURE OF THE ENGINEER. COPIED |
| SIGNATURES OR SIGNATURE STAMPS ARE NOT ACCEPTABLE. SEE |
| FS 471 AND FAC 61G15-23.002. |
| |
| 4) SUBMIT PRODUCT APPROVALS FOR THE PANEL WALLS, DOORS, |
| ETC. AS REQUIRED BY RULE 9B-72. PROVIDE TEST REPORTS |
| AND INSTALLATION INSTRUCTIONS. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. |
| |
| 5)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 6) THE PRINTED NAME OF THE ENGINEER IS ILLEGIBLE ON THE |
| SHEET CONTAINING THE DESIGN CRITERIA. PLEASE CORRECT. |
| |
| 7) PROVIDE STRUCTURAL DETAILS FOR THE 1'- 6" HIGH |
| CONCRETE KNEE WALL SHOWN ON SECTION 'A' OF THE |
| DRAWINGS. |
| |
| 8) DETAIL 'B' ON AN UN-NUMBERED SHEET SPECIFIES THE |
| WIND SPEED AS 130 MPH. PLEASE CORRECT. THE CITY OF WPB |
| HAS A WIND SPEED OF 140 MPH. |
| |
| 9) PLEASE NUMBER OR OTHER WISE IDENTIFY THE SHEETS OF |
| DRAWINGS THAT WERE SUBMITTED. FBC 106.1.3* AMENDED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |