Plan Review Notes
Plan Review Notes For Permit 07070454
Permit Number 07070454
Review Stop B
Sequence Number 4
Notes
Date Text
2007-09-17 16:39:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE RESPONSE LETTER STATED THAT I ASKED FOR ANCHOR
 SPACING BE CHANGED TO 4".THIS WAS NOT WHAT I
 INTENDED; I STATED THAT 4" WAS REQUIRED FOR SPANS OF
 12', WHICH WAS THE SPAN ON THE INSTALLATION SCHEDULE.
 A NEW INSTALLATION SCHEDULE HAS BEEN PROVIDED AND SPANS
 ARE FIXED.
  
 2.)SEE SHEET 14 OF THE PRODUCT APPROVAL.AN EDGE
 DISTANCE OF 3" REQUIRES A FACTOR OF .83 APPLIED TO THE
 ANCHOR SPACING.PLEASE REVISE.
  