2007-09-10 13:52:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PLEASE CLARIFY SPANS ON THE INSTALLATION SCHEDULE.
 THE SPAN SHOULD BE THE BLADE LENGTH, SO SHOULD
 CORRELATE WITH THE HEIGHT OF THE SHUTTER AND THE
 CONNECTION TYPE.FOR INSTANCE, OPENING 2, YOU'VE
 STATED THAT IT HAS A SPAN OF 12.1 FOR A 64" HIGH
 OPENING.ANCHOR SPACING IS COMPLIANT FOR A SPAN OF 6',
 BUT NOT 13' (4" SPACING REQUIRED RATHER THAN 10").
 PLEASE REVISE.