Date Text
2008-02-06 14:23:572004 FBC W/2007 REVISIONS
  
 THE REVISION TO ADD 2 X 6 BEARING WALL AND NEW BEAM IS
 DENIED
  
 1) ON SHEET A-4 THE NEW 2 X 6 BEARING WALL IS SPECIFIED
 AS AN EXISTING WALL ACCORDING TO THE WALL LEGEND.
 PLEASE REVISE. 2004 FBC 106.1.3* CITY AMENDMENTS.
  
 2) ON SHEET A-2 THE 2 X 6 BEARING WALL IS SPECIFIED AS
 A 4" WALL. IT WILL NEED TO BE REVISED. 2004 FBC
 106.1.3* CITY AMENDMENTS
  
 3) ON SHEET A-5 THE NEW ROOF GIRDER BEAM IS SPECIFIED
 AS 3 - 2 X 10S AND IN THE CONNECTOR SCHEDULE A SIMPSON
 LGUM 210-2, WHICH IS FOR A TWO MEMBER GIRDER IS
 SPECIFIED. PLEASE CORRECT. 2004 FBC 106.1.1* CITY
 AMENDMENTS.
  
 4) SUBMIT SIGNED AND SEALED CALCULATIONS FROM THE
 ENGINEER SHOWING THAT THE 3 -2 X 10 GIRDER SPANNING
 MORE THAN 15 FEET IS ADEQUATE TO RESIST THE ROOF LIVE
 AND DEAD LOADS WITH THE CEILING ATTACHED. 2004 FBC
 106.1.2* CITY AMENDMENTS.
  
 5) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE NEW TRUSSES AND RAFTERS TO THE 2 X 6 BEARING WALL.
 2004 FBC 106.1.3* CITY AMENDMENTS.
  
 6)PROVIDE A DETAIL OF THE 2 X 6 BEARING WALL
 SPECIFYING THE CONNECTORS, ANCHOR BOLTS, ETC. THAT WILL
 BE USED TO PROVIDE A CONTINUOUS LOAD PATH. FBC R601.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]