2007-10-25 08:14:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 9-19-07 NOTE #2. ENERGY
 CALCULATIONS LINE 15 IS TAKING CEILING FAN CREDIT, SEE
 FBC 13-607.2.A.3.1 CEILING FAN CREDIT MAY BE TAKEN IF
 ONE OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE
 BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED
 IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY
 ROOMS, OR GREAT ROOMS). PLEASE SHOW ON ELECTRICAL PLAN
 EXISTING CEILING FANS IN ALL REQUIRED ROOMS IF THEY
 EXIST OR REMOVE CREDIT FROM ENERGY CAL'S.
  
 2) AS NOTED IN LAST REVIEW 9-19-07 NOTE #3. I COULD NOT
 VERIFY THE A/C EQUIPMENT LISTED ON MECHANICAL PLAN WITH
 THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT ARI LISTING,
 SEE FBC 13-607.1.ABC.3.1.1.
  
 3) THE DUCT DESIGN MUST BE PART OF THE PLAN AND CAN NOT
 BE ADDED BY HAND TO SOME OTHER PLAN, PLEASE SUBMIT A
 PROPER MECHANICAL PLAN (NO PENCIL, PEN, WHITE-OUT, AND
 NO HAND CHANGES), SEE W.P.B. AMEND. 106.1.3..
  
 4) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]