2007-10-25 08:14:48 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| |
| 1) AS NOTED IN LAST REVIEW 9-19-07 NOTE #2. ENERGY |
| CALCULATIONS LINE 15 IS TAKING CEILING FAN CREDIT, SEE |
| FBC 13-607.2.A.3.1 CEILING FAN CREDIT MAY BE TAKEN IF |
| ONE OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE |
| BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED |
| IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY |
| ROOMS, OR GREAT ROOMS). PLEASE SHOW ON ELECTRICAL PLAN |
| EXISTING CEILING FANS IN ALL REQUIRED ROOMS IF THEY |
| EXIST OR REMOVE CREDIT FROM ENERGY CAL'S. |
| |
| 2) AS NOTED IN LAST REVIEW 9-19-07 NOTE #3. I COULD NOT |
| VERIFY THE A/C EQUIPMENT LISTED ON MECHANICAL PLAN WITH |
| THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT ARI LISTING, |
| SEE FBC 13-607.1.ABC.3.1.1. |
| |
| 3) THE DUCT DESIGN MUST BE PART OF THE PLAN AND CAN NOT |
| BE ADDED BY HAND TO SOME OTHER PLAN, PLEASE SUBMIT A |
| PROPER MECHANICAL PLAN (NO PENCIL, PEN, WHITE-OUT, AND |
| NO HAND CHANGES), SEE W.P.B. AMEND. 106.1.3.. |
| |
| 4) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR |
| TIMES THE FEE. |
| |