2007-09-19 15:01:48 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY THE |
| PREPARER, SEE FBC 13-103.1.1. |
| |
| 2) ENERGY CALCULATIONS LINE 15 IS TAKING CEILING FAN |
| CREDIT, SEE FBC 13-607.2.A.3.1 CEILING FAN CREDIT MAY |
| BE TAKEN IF ONE OR MORE CEILING FANS ARE INSTALLED IN |
| EACH OF THE BEDROOMS AND A MINIMUM OF ONE CEILING FAN |
| IS INSTALLED IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, |
| FAMILY ROOMS, OR GREAT ROOMS). PLEASE SHOW ON |
| ELECTRICAL PLAN EXISTING CEILING FANS IN ALL REQUIRED |
| ROOMS IF THEY EXIST OR REMOVE CREDIT FROM ENERGY |
| CAL'S. |
| |
| 3) I COULD NOT VERIFY THE A/C EQUIPMENT LISTED ON |
| MECHANICAL PLAN WITH THE ARI DIRECTORY WEB-SITE TO |
| CHECK SEER AND THAT IT IS A HEAT PUMP, PLEASE SUBMIT |
| ARI LISTING AND DETAILED MANUFACTURER'S SPECIFICATION'S |
| AND INSTALLATION INSTRUCTIONS FOR A/C SYSTEM. |
| |
| 4) THE MECHANICAL PLAN SUBMITTED HAS TO MUCH FLOOR PLAN |
| DETAIL ON IT AND IS DIFFICULT TO READ. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC |
| 106.1.1. |
| |
| 5) THE DUCT DESIGN MUST BE PART OF THE PLAN AND CAN NOT |
| BE ADDED BY HAND TO SOME OTHER PLAN, PLEASE SUBMIT A |
| PROPER MECHANICAL PLAN. |
| |
| 6) AN EXHAUST FAN IS REQUIRED IN THE MASTER BATHROOM |
| TUB AND SHOWER AREA, SEE RES.R303.3. |
| |
| 7) THE EXISTING BATHROOM REQUIRES A EXHAUST FAN , SEE |
| RES. R303.3. |
| |
| 8) PROVIDE FOR RETURN AIR TO THE EXISTING PART OF THE |
| HOUSE IF THE FAMILY ROOM DOORS WERE CLOSED, SEE RES. |
| M1602.4. |
| |
| 9) MECHANICAL PLAN WILL NEED TO BE SIGNED AND SEALED BY |
| THE ENGINEER AS HIS INFORMATION IS IN THE TITLE BLOCK, |
| IF HIS INFORMATION WAS NOT IN THE TITLE BLOCK THEN IT |
| WOULD NEED THE PREPARERS INFORMATION AND SIGNATURE, SEE |
| WPB 106.1.3. |
| |