| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| |
| 2} PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND |
| CONDUCTOR SIZES. |
| |
| 3} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| SMALL APPLIANCE CIRCUITS @ 1500 VA EACH, 2 MINIMUM, |
| 220.52(A). |
| |
| 4} } PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. |
| |
| 5} THE RISER DIAGRAM IS NOT CLEAR. INDICATE IF THERE IS |
| A METER/ MAIN OR A DISCONNECT DRAWN AS "2P "A". IF A |
| DISCONNECT IS LOCATED AT THE METER, AN EQUIPMENT GROUND |
| PER 250.122 MUST BE RAN WITH THE PANEL FEEDER. |
| |
| 6} SEE 250.52(A)(3) FOR FOOTER STEEL, INCLUDE AS PART |
| OF THE REQUIRED GEC SYSTEM WHEN RELOCATING THE SERVICE |
| AND PUTTING AN ADDITION ON, AS THE FOOTER STEEL IS |
| "AVAILABLE". |
| |
| 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED |
| IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON |
| PLAN. |
| |