Plan Review Notes
Plan Review Notes For Permit 07070447
Permit Number 07070447
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-19 07:56:22 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND
 CONDUCTOR SIZES.
  
 3} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
 SMALL APPLIANCE CIRCUITS @ 1500 VA EACH, 2 MINIMUM,
 220.52(A).
  
 4} } PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 5} THE RISER DIAGRAM IS NOT CLEAR. INDICATE IF THERE IS
 A METER/ MAIN OR A DISCONNECT DRAWN AS "2P "A". IF A
 DISCONNECT IS LOCATED AT THE METER, AN EQUIPMENT GROUND
 PER 250.122 MUST BE RAN WITH THE PANEL FEEDER.
  
 6} SEE 250.52(A)(3) FOR FOOTER STEEL, INCLUDE AS PART
 OF THE REQUIRED GEC SYSTEM WHEN RELOCATING THE SERVICE
 AND PUTTING AN ADDITION ON, AS THE FOOTER STEEL IS
 "AVAILABLE".
  
 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  