2007-08-08 10:14:41 | BUILDING PLAN REVIEW |
| PERMIT: 007070425 |
| ADD: 201 NARCISSUS AVE |
| CONT: ROYAL DIAMONS HOMES |
| TEL: (561)582-3818 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 1ST |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) 2004 FBC EXISTING |
| 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 303, 304 AND 305 OF THIS CODE. |
| |
| 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1, |
| 2004 SHALL BE DESIGNED TO THE 2004 |
| FLORIDA BUILDING CODE/WITH 2006 REVISIONS. |
| |
| 4)PROVIDE THE STRUCTURAL FLOOR LOAD CALCULATIONS FOR |
| THE FISH TANK AS INDICATEDON SHEET A-1.2 NOTE #7. |
| |
| 5)WHEN THE EXISTING FLOOR IS REMOVED, WHAT TYPE OF |
| MATERIAL WILL BE USED TO REPLACE IT?PROVIDE |
| INFORMATIONON THE SOUND INSULATION. FBC 1207.3 THE |
| FLOOR/CEILINGASSEMBLIES BETWEEN DWELLING UNITS SHALL |
| HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF NOT |
| LESS THAN 50. SEE FBC 1207 FOR MORE INFORMATION. |
| |
| 6)PROVIDE A FINISH SCHEDULE INDICATING THE FINISHES |
| ON THE FLOOR/CEILINGS AND WALLS. SEE FBC 803/804 AND |
| 805. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |