Plan Review Notes
Plan Review Notes For Permit 07070389
Permit Number 07070389
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-20 16:22:34 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC. INDICATE OCP AND CONDUCTOR SIZES SO
 THAT THE REQUIRED CIRCUITS CAN BE REVIEWED FOR
 COMPLIANCE.
  
 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 4} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.
  
 5} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS. INDICATE THE LOCATION ON
 THE PLANS.
  
 6} 440.14 LOCATION
 DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT FROM
 AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING OR
 REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS SHALL
 BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT.
  
 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON
 THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]