2007-11-16 12:13:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) PLANS ON FILE PAGE A-7.2 SHOWS THE WALLS TO THE
 TEL/SERVER ROOM ARE ONE HOUR FIRE RATED. THE TWO 14"
 FLEX DUCTS MAY NOT PENETRATE A RATED WALL, SHOW
 COMPLIANCE WITH 2004 FBC/M 607.5. ALSO FOR THE 8'
 EXHAUST DUCT (ON PAGE M-2.1).
  
 MECHANICAL PLAN REVIEW BY;