Plan Review Notes
Plan Review Notes For Permit 07070387
Permit Number 07070387
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-04 12:26:432007-09-04 12:26:43
  
 ** DENIED2ND REVIEW**
  
  
 ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE SEE THERE ARE ALSO NEW COMMENTS AS THERE WERE
 SEVERAL CHANGES MADE TO PANEL SCHEDULES/RISER WHICH
 HAVE CREATED NEW COMMENTS. AS THESE ITEMS WERE NOT ON
 PREVIOUS PLANS THIS WAY, THESE NEW COMMENTS COULD NOT
 HAVE BEEN MADE ON THE PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WITH RESPECT TO
 CODES REQUIRED. PLEASE SEE ARCHITECTURAL COVER SHEET
 WHICH NOTES A 2005 NFPA-72. PLEASE KNOW THIS CODE
 SHOULD BE THE 2002 NFPA-72.
 PLEASE ADJUST.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY REQUIRE CERTAIN CODES.
  
 2) NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS REVIEW WITH
 RESPECT TO INFORMATION BEING NEEDED FOR MAXIMUM
 LIGHTING POWER DENSITIES. PLEASE SEE 13-415.2, AND
 13-415.2.ABC.1.2 WITH RESPECT TO TRACK LIGHTING. THE
 RESPONSE FROM THE DESIGNER MENTIONS LOADS FOR TRACK
 LIGHTING BASED ON THE NEC MINIMUM LOADS FOR BRANCH
 CIRCUITS AND SERVICE FEEDER LOADS. THIS SECTION OF THE
 FBC AND CHAPTER 13 HAS TO DO WITH THE MAXIMUM ALLOWED
 LIGHTING LEVELS AND WATTS PER SQ FT BASED ON USE OF THE
 SPACE ETC.
 PLEASE SEE THERE IS A MAXIMUM TIME OF 30 MINUTES FOR
 OCCUPANCY TYPE DEVICES PER THE FBC AND SOME OC TYPE
 DEVICES AS NOTED ON LEGEND MENTIONS 2HRS.
 PLEASE SEE THAT THE COORDINATION OF LIGHTING, FIXTURES
 AND LEVELS CAN NOT FULLY BE DONE AT THIS TIME. PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #8 WITH
 RESPECT TO MINIMUM LEVELS FOR ADA COMPLIANCE. THE
 RESPONSE LETTER MENTIONS LEVELS AT 70DB, HOWEVER NO
 INFORMATION OR LEVELS FOR CANDELA LEVELS COULD BE
 LOCATED.
 PLEASE SEE THE NOTE BELOW FROM PREVIOUS REVIEW*PLEASE
 SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE THE
 MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA REQUIRED
 AREAS. DEVICES ARE BEING SHOWN ON PLANS/LEGEND. PLEASE
 CORRELATE WITH PLANS, AND FA SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 4) NOTE:PLEASE SEE PREVIOUS NOTE #10. RESPONSE
 MENTIONS LOAD WAS ADJUSTED HOWEVER PLANS SHOW THE SAME
 INFORMATION AS ON PREVIOUS CALCULATIONS. PLEASE SEE THE
 NEC HANDBOOK AS WATER HEATERS ARE NOW CONSIDERED
 *CONTINUOUS LOADS* WHICH REQUIRES THE 125% FOR LOAD.
 THIS WAS A CHANGE FROM THE PREVIOUS CODE WHICH ONLY
 REQUIRED THE BRANCH CIRCUIT CONDUCTORS AND OVER CURRENT
 PROTECTION TO BE DONE AT 125%.
 PLEASE ALSO INCLUDE THE WATER HEATER LOAD AT 125% FOR
 CONTINUOUS LOAD. PLEASE SEE 422.13 OF THE 2005 NEC.
  
 5) NOTE: PLEASE SEE THE PREVIOUS NOTE #11 REQUESTED
 COORDINATION AND CHANGES FOR CODE COMPLIANCE FOR
 FEEDERS ON RISER AND PANEL SCHEDULES. PLEASE SEE SOME
 OF THESE ITEMS WERE CHANGED AND CORRECT HOWEVER PLEASE
 SEE SOME ITEMS WERE NOT CHANGED.
 PLEASE SEE THE FEEDERS NOTED ON PANEL *H* ARE STILL
 SHOWN AS 3/0 WHEN THE RISER AND NOTES TO RISER INDICATE
 1/0.
 PLEASE SEE COMMENTS BELOW FOR OTHER ITEMS FOR
 COORDINATION.
  
 6) NOTE: PLEASE SEE THE PREVIOUS NOTE #12 WHICH
 REQUESTED FOR THE OVER CURRENT PROTECTION OF THE
 TRANSFORMER AS LISTED ON THE PANEL *H* TO MEET 450.3.
 THE RESPONSE LETTER MENTIONS THIS IS TO BE CHANGED TO
 70AMP HOWEVER PLEASE SEE PANEL *H* AS THIS NOW SHOW A
 3-POLE 20AMP BREAKER WITH #3 CONDUCTORS.
 PLEASE SEE THE RISER SHOWS OTHER CONDUCTOR SIZES.
 PLEASE KNOW THE #3 CONDUCTORS WILL NOT FIT INTO THIS
 SIZE BREAKER.
 PLEASE SEE THIS 20AMP OVER CURRENT PROTECTION DOES NOT
 MEET THE MINIMUM LOADS ON THE TRANSFORMER FROM PANEL
 *L1*.
 240.4, 310.16, 110.3,ETC. THERE ARE SEVERAL CODE
 SECTIONS, TOO MANY TO LIST.
 PLEASE COORDINATE.
  
 7) NOTE: PLEASE SEE THE LOAD FOR THE TRANSFORMER HAS
 NOW BEEN REVISED AND INDICATES A LOAD OF .5 KVA. THIS
 IS NOT POSSIBLE WHEN THE LOAD ON PANEL *L1* IS 42KVA AT
 120/208 VOLTS. THIS LOAD WAS CHANGED FROM PREVIOUS
 PLANS.
 PLEASE SEE THE TOTAL LOAD ON PANEL *H* HAS NOW GONE
 DOWN WITH OUT THIS LOAD OF THE PANEL *L1*.
 PLEASE COORDINATE AND ADJUST ALL OF THESE ITEMS.
 240,220, 408.4, 310.16, 215, ETC.
  
 8) NOTE: PLEASE SEE PREVIOUS NOTE #14. PLEASE CLARIFY
 RATING OF THE PANELS *H* AND *L1*ON RISER AND ON
 SCHEDULE.
 PANEL *L1* IS SHOWN AS A 225AMP RATED PANEL WITH A
 150AMP MCB, YET RISER SHOWS THIS AS 200AMPS? PLEASE SEE
 PANEL *H* IS SHOWN ON SCHEDULE AS 225AMP RATED, WITH
 200AMP RATED MCB. THIS IS OK, HOWEVER THIS IS SHOWN AS
 200AMP ON RISER WITH A 150AMP FEED FROM THE BUS-TAP AND
 DISCONNECT.
 THE ABOVE NEEDS SOME COORDINATION.
 FBC 106.1.2, 106.1.1, 106.3.5.1.2
 FAC 61G15-23.004
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE #16 AS THIS REQUESTED
 COORDINATION OF THE PANEL NUMBER OF POLES LISTED ON
 PANEL AND SHOWN ON CIRCUITS.
 PLEASE SEE PANEL *L1* WAS CORRECTED, HOWEVER PLEASE SEE
 PANEL *H* IS STILL SHOWN AS 30 AND 42 CIRCUIT PANELS.
 (225AMP RATED PANELS ARE MOST LIKELY NOT AVAILABLE AS
 30POLES)
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #17 FOR TRANSFORMER
 GROUNDING. A CONDUCTOR SIZE WAS ADDED HOWEVER NO
 ATTACHMENT LOCATIONS WERE SHOWN OR NOTED.
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE TRANSFORMER GROUNDING ELECTRODE
 SYSTEM PER 250.20, 250.30, 250.66 ETC. PLEASE SHOW
 ATTACHMENT WITH THE SIZE OF THE CONDUCTOR. FBC 106.1.2,
 106.3.5.1.2, FAC 61G15-33.004
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 PLEASE BE SURE TO CALL TO GO OVER COMMENTS.
  
 AS PREVIOUSLY STATED:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]