Plan Review Notes
Plan Review Notes For Permit 07070387
Permit Number 07070387
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-20 11:36:53*** DENIED ***
 1) PLEASE ADJUST NOTE ON MECHANICAL PLANS "CEILING
 CAVITY IS A RETURN AIR PLENUM NO P.V.C. ALLOWED" TO
 INCLUDE NO COMBUSTIBLES TO COMPLY WITH 2004 FCC/M
 602.2.1.
  
 2) PLAN M-2 SHOWS A BATHROOM EXHAUST DUCT IN THE RETURN
 AIR PLENUM, PER 2004 FBC/M 601.3 EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHELL NOT PASS THROUGH PLENUMS.
 PLEASE CORRECT.
  
 3) IF AN EXHAUST DUCT NOT UNDER PRESSURE IS TO BE USED
 SHOW HOW THE OPENING WILL BE PROTECTED AT THE RATED
 WALL, SEE 2004 FBC/M 607.
  
 4) BATHROOM EXHAUST FAN EF-1 IS RATED AT 50 CFM'S. SEE
 2004 FBC/M TABLE 403.3 SHOWS TOILET ROOMS AT 50 CFM'S
 AND SHOWER AT 50 CFM'S. PLEASE ADJUST.
  
 5) PLAN M-3 SHOWS A DETAIL FOR A CONDENSER UNIT WALL
 BRACKET. PLEASE SUBMIT ENGINEERING FOR BRACKET AND SHOW
 THAT IT WILL WITHSTAND 140 MPH WINDS TO COMPLY WITH
 2004 FBC 1609. IF PRE-ENGINEERED PLEASE SUBMIT PRODUCT
 APPROVAL, PER FAC RULE 9B-72.
  
 6) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK ON
 MECHANICAL PLANS, PER 2004 FBC CITY WPB AMEND.
 106.1.3.
  
 7) SEE ELECTRICAL REVIEW NOTES #1 AND #2, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.