Plan Review Notes For Permit 07070387 |
Permit Number |
07070387 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-20 11:36:53 | *** DENIED *** | | 1) PLEASE ADJUST NOTE ON MECHANICAL PLANS "CEILING | | CAVITY IS A RETURN AIR PLENUM NO P.V.C. ALLOWED" TO | | INCLUDE NO COMBUSTIBLES TO COMPLY WITH 2004 FCC/M | | 602.2.1. | | | | 2) PLAN M-2 SHOWS A BATHROOM EXHAUST DUCT IN THE RETURN | | AIR PLENUM, PER 2004 FBC/M 601.3 EXHAUST DUCTS UNDER | | POSITIVE PRESSURE SHELL NOT PASS THROUGH PLENUMS. | | PLEASE CORRECT. | | | | 3) IF AN EXHAUST DUCT NOT UNDER PRESSURE IS TO BE USED | | SHOW HOW THE OPENING WILL BE PROTECTED AT THE RATED | | WALL, SEE 2004 FBC/M 607. | | | | 4) BATHROOM EXHAUST FAN EF-1 IS RATED AT 50 CFM'S. SEE | | 2004 FBC/M TABLE 403.3 SHOWS TOILET ROOMS AT 50 CFM'S | | AND SHOWER AT 50 CFM'S. PLEASE ADJUST. | | | | 5) PLAN M-3 SHOWS A DETAIL FOR A CONDENSER UNIT WALL | | BRACKET. PLEASE SUBMIT ENGINEERING FOR BRACKET AND SHOW | | THAT IT WILL WITHSTAND 140 MPH WINDS TO COMPLY WITH | | 2004 FBC 1609. IF PRE-ENGINEERED PLEASE SUBMIT PRODUCT | | APPROVAL, PER FAC RULE 9B-72. | | | | 6) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK ON | | MECHANICAL PLANS, PER 2004 FBC CITY WPB AMEND. | | 106.1.3. | | | | 7) SEE ELECTRICAL REVIEW NOTES #1 AND #2, PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|