Plan Review Notes
Plan Review Notes For Permit 07070387
Permit Number 07070387
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-30 10:25:41***DENIED***
  
 1) DOOR SCHEDULE INDICATES A "C" RATING FOR
 ELECTRICAL/MECHANICAL DOOR. PLEASE PROVIDE RATING IN
 TERMS OF MINUTES.
  
 2) PLEASE INDICATE UL LISTED CLOSER FOR APPROPRIATE
 DOOR.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 5) PLEASE INDICATE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN TERMS OF CLASS
 A,B ORC.
  
 6) WORK SHALL NOT INTERFERE WITH EXISTING BUILDING FIRE
 PROTECTION EQUIPMENT AND REQUIRED MEANS OF EGRESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756