Plan Review Notes
Plan Review Notes For Permit 07070387
Permit Number 07070387
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-19 16:54:35 
  
 ****** UNSAT *****
  
  
  
 1) NOTE: PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR
 PERMIT AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT
 UNDER THE NEW CODES.
 PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE
 ARCHITECTURAL CS COVER SHEET. PLEASE ALSO BE SURE THE
 TRADES REFLECT THE CODES RELEVANT TO THEIR DESIGNS ON
 RESPECTIVE SHEETS.
 2004 FBC W/ 2006 REVISIONS (ALL TRADES).
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2003 NFPA-20
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY REQUIRE CERTAIN CODES.
  
 2) NOTE: PLEASE SEE MISSING THE REQUIRED INFORMATION ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE A
 CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS SHOWN ON
 TITLE BLOCKS IS ONLY APPLIED FOR AND IS AN APPLICATION
 IN PROGRESS AS LISTED ON THE STATES WEBSITE AS OF THIS
 REVIEW. PLEASE REVISE TITLE BLOCKS FOR COMPLIANCE WITH
 THE FS 481.0219, FAC 61G1-16.004 OR OBTAIN THE CA # BY
 THE TIME THE NEXT RE-SUBMITTAL OF PLANS IS DONE. **
 THIS COMMENT STANDS FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULE(S) SUBMITTED. PLEASE
 SEE SOME ARE MISSING CIRCUIT DESIGNATIONS.
 FBC 106.3.5.1.2, 106.1.2, NEC 408.4
  
 4) NOTE: PLEASE SEE NEC 408.4 AS THE CIRCUITS ARE
 REQUIRED TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. PLEASE SEE THE DESIGNATIONS MAY BE NUMERICAL
 TO ROOMS/AREAS.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.5.1.2
  
 5) NOTE: PLEASE SEE THE PLANS WILL REQUIRE AN
 ADDRESSING REVIEW. PLEASE SEE THE PERMIT APPLICATION
 DOES NOT INCLUDE ANY SUITE/UNIT NUMBER. ONCE THE
 SUITE/UNIT NUMBER IS DESIGNATED PLEASE REVISE TITLE
 BLOCKS TO INCLUDE THE SUITE/UNIT NUMBER.
 FBC 106.1.2
 FAC 61G1-16.004/61G15-23.002
  
 6) NOTE:
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. P PLEASE
 ALSO SEE 13-415.2
 PLEASE SEE THAT THE TIMES FOR SCHEDULING NEEDS TO BE
 STATED ON PLANS FOR LIGHTING CONTROL PANEL(S). PLEASE
 KNOW EVEN THOUGH THE TIME IS DERIVED FROM THE TENANT
 AND WILL MOST LIKELY CHANGE THE PLANS ARE STILL
 REQUIRED TO CONTAIN A MINIMUM TIMED SCHEDULE. PLEASE
 STATE ALL MAXIMUM TIMES FOR THE DEVICES AS SHOWN ON
 PLANS. PLEASE COORDINATE THE INFORMATION ON THE SYMBOL
 LEGEND. (SOME MAXIMUM TIMES ARE SHOWN BUT NOT FOR ALL
 DEVICES AS SPECIFIED).
 PLEASE SEE AREA(S) WHICH DO NOT CONTAIN DEVICES FOR
 COVERAGE. PLEASE CLARIFY THE PRIVATE BATH/STALL AREA
 WHICH CONTAINS SEPARATION WALL. IS THE DEVICE AS SHOWN
 A COMBINATION DEVICE WHICH PICKS UP ON
 MOTION/SOUND/HEAT?
 PLEASE COMPLETE FIXTURE LEGEND FOR THE TYPES OF
 LUMINARIES, THE NUMBER OF LUMINARIES, ETC. PLEASE SEE
 SOME AREAS OF THE FIXTURE LEGEND WHICH DID NOT PRINT
 CORRECTLY AND SEEMS TO HAVE COMPACTED SOME LINES AND
 DELETED INFORMATION.
 PLEASE SEE THE NUMBER OF LUMINARIES ON PLANS DO NOT
 CORRELATE WITH THE NUMBER OF LUMINARIES ON LEGEND.
 (EXAMPLE PLEASE SEE FIXTURE R1) THE PLANS INDICATE A
 MUCH HIGHER NUMBER OF THESE LUMINARIES THAN THAT
 INDICATED ON LEGEND).
 PLEASE CLARIFY THE LOADS FIGURED FOR THE TRACK LIGHTING
 PER 13-415.2.ABC.1.2
 PLEASE KNOW THAT THERE IS INFORMATION NEEDED FOR SOME
 OF THE ABOVE WHICH AT THIS TIME CAN NOT CONFIRMED FOR
 COMPLIANCE.
  
 7) NOTE: PLEASE CLARIFY WHAT IS BEING SHOWN AS
 *COMPUTER ROOM*. IS THIS AN *IT* ROOM? THIS CAN BE
 CLARIFIED WITH NOTE(S) ON PLANS.
 IF THIS ROOM WILL FALL UNDER THE DEFINITIONS OF AN IT
 ROOM, PLEASE ADJUST PLANS FOR CODE COMPLIACE FOR NEC
 645 AND NFPA-75.
  
 8) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE 210.63 AND 210.8B FOR MISSING CU
 GFI. IS THIS EXISTING OR NEW?
  
 10) NOTE: PLEASE ALSO INCLUDE THE WATER HEATER LOAD AT
 125% FOR CONTINUOUS LOAD. PLEASE SEE 422.13 OF THE 2005
 NEC.
  
 11) NOTE: PLEASE SEE THE FEEDERS TO TRANSFORMER FROM
 PANEL *H* DO NOT CORRELATE FROM RISER DIAGRAM TO PANEL
 *H* SCHEDULE.
 PLEASE SEE THAT THE FEEDERS ON PANEL H ARE OK, HOWEVER
 THE RISER DO NOT MEET 310.16. PLEASE SEE THE FOLLOWING
 COMMENT #12 AS THE OCP ON THE PANEL WILL BE REQUIRED TO
 CHANGE WHICH WILL AFFECT THE CONDUCTOR SIZES. PLEASE BE
 SURE TO COORDINATE RISER, PANEL AND CONDUCTOR SCHEDULE
 ON THE UPPER RIGHT HAND CORNER.
  
 12) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT
 PROTECTION OF THE 45K TRANSFORMER IS TOO HIGH. PLEASE
 SEE THIS IS 125% MAXIMUM UNLESS MEETING THE EXCEPTIONS
 OF THE TABLES AS NOTED.
 PLEASE ADJUST FEEDERS.
  
 13) NOTE: PLEASE SEE THE FEEDERS ON THE SECONDARY SIDE
 OF THE TRANSFORMER DO NOT MEET 240.21, 310.16 AND
 240.4.
 PLEASE SEE THE CONDUCTORS MUST TERMINATE IN OCP WHICH
 LIMITS THE LOAD ON THESE TAPPED CONDUCTORS.
 PLEASE SEE THE 200AMP OCP IN PANEL L1 IS TOO HIGH FOR
 THE #1 CONDUCTORS SHOWN ON RISER.
  
 14) NOTE: PLEASE CORRELATE RISER FOR PANEL H WITH THAT
 OF THE CONDUCTORS SHOWN ON PANEL H SCHEDULE.
 THIS PANEL IS LISTED AS 225A, 200A MCB AND 3/0
 CONDUCTORS WHERE PANEL IS LISTED AS MLO?
 PLEASE SEE THE COMMENTS ABOVE WITH RESPECT TO
 COORDINATION OF CONDUCTORS ETC.
 FBC 106.1.2., FAC 61G15-33.004
 NEC 310.16,240.4
  
 15) NOTE: PLEASE CORRELATE PANEL L1 WITH RISER. PLEASE
 SEE THIS PANEL SCHEDULE AND INFORMATION INDICATES THIS
 AS A 225A PANEL/200AMP MCB. THIS IS ALSO SHOWN AS
 CONTAINING MLO WITH 3/0 CONDUCTORS, YET RISER SHOWS #1
 AWG?
 PLEASE COORDINATE ALL.
 FBC 106.1.2, FAC 61G15-33.004
 NEC 310.16, 240.4
  
 16) NOTE: PLEASE SEE BOTH PANELS H AND L1 INDICATE
 30POLES ON SCHEDULE HOWEVER THEY ARE CIRCUITED TO 42
 POLES?
 PLEASE COORDINATE.
 FBC 106.1.2.
  
 17) NOTE: PLEASE INDICATE THE TRANSFORMER GROUNDING
 ELECTRODE SYSTEM PER 250.20, 250.30, 250.66 ETC. PLEASE
 SHOW ATTACHMENT WITH THE SIZE OF THE CONDUCTOR. FBC
 106.1.2, 106.3.5.1.2, FAC 61G15-33.004
  
 18) NOTE: PLEASE CLARIFY THE AIC RATINGS FOR BREAKERS
 IN PANELS. THESE ARE BEING NOTED AS 22K FOR ALL
 BREAKERS IN PANELS INCLUDING BRANCH CIRCUITS. THIS IS
 OK AND CODE COMPLIANT, HOWEVER THE NOTE ON PANEL ALSO
 STATES SERIES RATING.
 PLEASE CLARIFY
 FBC 106.1.2.
  
 19) NOTE: PLEASE PROVIDE INFORMATION FOR THE ACCESS
 CONTROL LOCKS. PLEASE SEE 7.2.1.5.1, 7.2.1.6.2 OF THE
 2003 LIFE SAFETY CODE AS THESE DEVICES SHALL NOT
 INTERFERE OR IMPEDE EGRESS.
 PLEASE PROVIDE FAIL SAFE INFORMATION.
 PLEASE SEE FIRE REVIEW COMMENTS AS THIS COMMENT MAY BE
 EXPANDED UPON. PLEASE VERIFY ANY ADDITIONAL INFORMATION
 ONCE THE FIRE MARSHAL HAS REVIEWED SAID PLANS.
  
 ** PLEASE SEE AS THERE ARE SEVERAL CHANGES WHICH NEED
 TO BE MADE TO PLANS/RISER, THERE MAY VERY WELL BE
 COMMENTS BASED ON CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-19 07:07:52IN ELEC FOR REVIEW.