Date |
Text |
2007-07-19 16:54:35 | |
| |
| ****** UNSAT ***** |
| |
| |
| |
| 1) NOTE: PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR |
| PERMIT AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT |
| UNDER THE NEW CODES. |
| PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE |
| ARCHITECTURAL CS COVER SHEET. PLEASE ALSO BE SURE THE |
| TRADES REFLECT THE CODES RELEVANT TO THEIR DESIGNS ON |
| RESPECTIVE SHEETS. |
| 2004 FBC W/ 2006 REVISIONS (ALL TRADES). |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| 2003 NFPA-20 |
| |
| ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| MAY REQUIRE CERTAIN CODES. |
| |
| 2) NOTE: PLEASE SEE MISSING THE REQUIRED INFORMATION ON |
| TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE A |
| CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS SHOWN ON |
| TITLE BLOCKS IS ONLY APPLIED FOR AND IS AN APPLICATION |
| IN PROGRESS AS LISTED ON THE STATES WEBSITE AS OF THIS |
| REVIEW. PLEASE REVISE TITLE BLOCKS FOR COMPLIANCE WITH |
| THE FS 481.0219, FAC 61G1-16.004 OR OBTAIN THE CA # BY |
| THE TIME THE NEXT RE-SUBMITTAL OF PLANS IS DONE. ** |
| THIS COMMENT STANDS FOR ALL SHEETS AND FOR ALL TRADES |
| WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| |
| 3) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| CORRELATE WITH THE PANEL SCHEDULE(S) SUBMITTED. PLEASE |
| SEE SOME ARE MISSING CIRCUIT DESIGNATIONS. |
| FBC 106.3.5.1.2, 106.1.2, NEC 408.4 |
| |
| 4) NOTE: PLEASE SEE NEC 408.4 AS THE CIRCUITS ARE |
| REQUIRED TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH |
| THEY FEED. PLEASE SEE THE DESIGNATIONS MAY BE NUMERICAL |
| TO ROOMS/AREAS. |
| PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM |
| THE NEC. |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.5.1.2 |
| |
| 5) NOTE: PLEASE SEE THE PLANS WILL REQUIRE AN |
| ADDRESSING REVIEW. PLEASE SEE THE PERMIT APPLICATION |
| DOES NOT INCLUDE ANY SUITE/UNIT NUMBER. ONCE THE |
| SUITE/UNIT NUMBER IS DESIGNATED PLEASE REVISE TITLE |
| BLOCKS TO INCLUDE THE SUITE/UNIT NUMBER. |
| FBC 106.1.2 |
| FAC 61G1-16.004/61G15-23.002 |
| |
| 6) NOTE: |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. P PLEASE |
| ALSO SEE 13-415.2 |
| PLEASE SEE THAT THE TIMES FOR SCHEDULING NEEDS TO BE |
| STATED ON PLANS FOR LIGHTING CONTROL PANEL(S). PLEASE |
| KNOW EVEN THOUGH THE TIME IS DERIVED FROM THE TENANT |
| AND WILL MOST LIKELY CHANGE THE PLANS ARE STILL |
| REQUIRED TO CONTAIN A MINIMUM TIMED SCHEDULE. PLEASE |
| STATE ALL MAXIMUM TIMES FOR THE DEVICES AS SHOWN ON |
| PLANS. PLEASE COORDINATE THE INFORMATION ON THE SYMBOL |
| LEGEND. (SOME MAXIMUM TIMES ARE SHOWN BUT NOT FOR ALL |
| DEVICES AS SPECIFIED). |
| PLEASE SEE AREA(S) WHICH DO NOT CONTAIN DEVICES FOR |
| COVERAGE. PLEASE CLARIFY THE PRIVATE BATH/STALL AREA |
| WHICH CONTAINS SEPARATION WALL. IS THE DEVICE AS SHOWN |
| A COMBINATION DEVICE WHICH PICKS UP ON |
| MOTION/SOUND/HEAT? |
| PLEASE COMPLETE FIXTURE LEGEND FOR THE TYPES OF |
| LUMINARIES, THE NUMBER OF LUMINARIES, ETC. PLEASE SEE |
| SOME AREAS OF THE FIXTURE LEGEND WHICH DID NOT PRINT |
| CORRECTLY AND SEEMS TO HAVE COMPACTED SOME LINES AND |
| DELETED INFORMATION. |
| PLEASE SEE THE NUMBER OF LUMINARIES ON PLANS DO NOT |
| CORRELATE WITH THE NUMBER OF LUMINARIES ON LEGEND. |
| (EXAMPLE PLEASE SEE FIXTURE R1) THE PLANS INDICATE A |
| MUCH HIGHER NUMBER OF THESE LUMINARIES THAN THAT |
| INDICATED ON LEGEND). |
| PLEASE CLARIFY THE LOADS FIGURED FOR THE TRACK LIGHTING |
| PER 13-415.2.ABC.1.2 |
| PLEASE KNOW THAT THERE IS INFORMATION NEEDED FOR SOME |
| OF THE ABOVE WHICH AT THIS TIME CAN NOT CONFIRMED FOR |
| COMPLIANCE. |
| |
| 7) NOTE: PLEASE CLARIFY WHAT IS BEING SHOWN AS |
| *COMPUTER ROOM*. IS THIS AN *IT* ROOM? THIS CAN BE |
| CLARIFIED WITH NOTE(S) ON PLANS. |
| IF THIS ROOM WILL FALL UNDER THE DEFINITIONS OF AN IT |
| ROOM, PLEASE ADJUST PLANS FOR CODE COMPLIACE FOR NEC |
| 645 AND NFPA-75. |
| |
| 8) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA |
| SHEETS SUBMITTED. |
| ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| SETS. |
| FBC 106.3.5.1.2 |
| |
| 9) NOTE: PLEASE SEE 210.63 AND 210.8B FOR MISSING CU |
| GFI. IS THIS EXISTING OR NEW? |
| |
| 10) NOTE: PLEASE ALSO INCLUDE THE WATER HEATER LOAD AT |
| 125% FOR CONTINUOUS LOAD. PLEASE SEE 422.13 OF THE 2005 |
| NEC. |
| |
| 11) NOTE: PLEASE SEE THE FEEDERS TO TRANSFORMER FROM |
| PANEL *H* DO NOT CORRELATE FROM RISER DIAGRAM TO PANEL |
| *H* SCHEDULE. |
| PLEASE SEE THAT THE FEEDERS ON PANEL H ARE OK, HOWEVER |
| THE RISER DO NOT MEET 310.16. PLEASE SEE THE FOLLOWING |
| COMMENT #12 AS THE OCP ON THE PANEL WILL BE REQUIRED TO |
| CHANGE WHICH WILL AFFECT THE CONDUCTOR SIZES. PLEASE BE |
| SURE TO COORDINATE RISER, PANEL AND CONDUCTOR SCHEDULE |
| ON THE UPPER RIGHT HAND CORNER. |
| |
| 12) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT |
| PROTECTION OF THE 45K TRANSFORMER IS TOO HIGH. PLEASE |
| SEE THIS IS 125% MAXIMUM UNLESS MEETING THE EXCEPTIONS |
| OF THE TABLES AS NOTED. |
| PLEASE ADJUST FEEDERS. |
| |
| 13) NOTE: PLEASE SEE THE FEEDERS ON THE SECONDARY SIDE |
| OF THE TRANSFORMER DO NOT MEET 240.21, 310.16 AND |
| 240.4. |
| PLEASE SEE THE CONDUCTORS MUST TERMINATE IN OCP WHICH |
| LIMITS THE LOAD ON THESE TAPPED CONDUCTORS. |
| PLEASE SEE THE 200AMP OCP IN PANEL L1 IS TOO HIGH FOR |
| THE #1 CONDUCTORS SHOWN ON RISER. |
| |
| 14) NOTE: PLEASE CORRELATE RISER FOR PANEL H WITH THAT |
| OF THE CONDUCTORS SHOWN ON PANEL H SCHEDULE. |
| THIS PANEL IS LISTED AS 225A, 200A MCB AND 3/0 |
| CONDUCTORS WHERE PANEL IS LISTED AS MLO? |
| PLEASE SEE THE COMMENTS ABOVE WITH RESPECT TO |
| COORDINATION OF CONDUCTORS ETC. |
| FBC 106.1.2., FAC 61G15-33.004 |
| NEC 310.16,240.4 |
| |
| 15) NOTE: PLEASE CORRELATE PANEL L1 WITH RISER. PLEASE |
| SEE THIS PANEL SCHEDULE AND INFORMATION INDICATES THIS |
| AS A 225A PANEL/200AMP MCB. THIS IS ALSO SHOWN AS |
| CONTAINING MLO WITH 3/0 CONDUCTORS, YET RISER SHOWS #1 |
| AWG? |
| PLEASE COORDINATE ALL. |
| FBC 106.1.2, FAC 61G15-33.004 |
| NEC 310.16, 240.4 |
| |
| 16) NOTE: PLEASE SEE BOTH PANELS H AND L1 INDICATE |
| 30POLES ON SCHEDULE HOWEVER THEY ARE CIRCUITED TO 42 |
| POLES? |
| PLEASE COORDINATE. |
| FBC 106.1.2. |
| |
| 17) NOTE: PLEASE INDICATE THE TRANSFORMER GROUNDING |
| ELECTRODE SYSTEM PER 250.20, 250.30, 250.66 ETC. PLEASE |
| SHOW ATTACHMENT WITH THE SIZE OF THE CONDUCTOR. FBC |
| 106.1.2, 106.3.5.1.2, FAC 61G15-33.004 |
| |
| 18) NOTE: PLEASE CLARIFY THE AIC RATINGS FOR BREAKERS |
| IN PANELS. THESE ARE BEING NOTED AS 22K FOR ALL |
| BREAKERS IN PANELS INCLUDING BRANCH CIRCUITS. THIS IS |
| OK AND CODE COMPLIANT, HOWEVER THE NOTE ON PANEL ALSO |
| STATES SERIES RATING. |
| PLEASE CLARIFY |
| FBC 106.1.2. |
| |
| 19) NOTE: PLEASE PROVIDE INFORMATION FOR THE ACCESS |
| CONTROL LOCKS. PLEASE SEE 7.2.1.5.1, 7.2.1.6.2 OF THE |
| 2003 LIFE SAFETY CODE AS THESE DEVICES SHALL NOT |
| INTERFERE OR IMPEDE EGRESS. |
| PLEASE PROVIDE FAIL SAFE INFORMATION. |
| PLEASE SEE FIRE REVIEW COMMENTS AS THIS COMMENT MAY BE |
| EXPANDED UPON. PLEASE VERIFY ANY ADDITIONAL INFORMATION |
| ONCE THE FIRE MARSHAL HAS REVIEWED SAID PLANS. |
| |
| ** PLEASE SEE AS THERE ARE SEVERAL CHANGES WHICH NEED |
| TO BE MADE TO PLANS/RISER, THERE MAY VERY WELL BE |
| COMMENTS BASED ON CHANGES. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-07-19 07:07:52 | IN ELEC FOR REVIEW. |