2007-10-30 09:16:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 7-18-07 NOTE #1. ENERGY
 CALCULATIONS SHOW THE RETURN AIR DUCTS ARE IN A
 CONDITIONED SPACE, MECHANICAL PLANS SHOW THEM IN THE
 ATTIC, SEE FBC 13-103.2. SAME ENERGY CAL'S WERE
 RESUBMITTED. PLEASE CORRECT ENERGY CALCULATIONS.
  
 2) AS NOTED IN LAST REVIEW 7-18-07 NOTE #2. ENERGY
 CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER
 2004 FBC 13-600.3.ABC.2. SAME ENERGY CAL'S WERE
 RESUBMITTED. PLEASE CORRECT.
  
 3) AS NOTED IN LAST REVIEW 7-18-07 NOTE #4. SEE YELLOW
 HIGH LIGHT ON MECHANICAL PLAN, SUPPLY AIR DUCT NEEDS TO
 BE SIZED, SEE WPB AMEND. 106.3.5.4 (10).
  
 4) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  