Plan Review Notes
Plan Review Notes For Permit 07070363
Permit Number 07070363
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-18 15:28:56*** DENIED ***
 1) ENERGY CALCULATIONS SHOW THE RETURN AIR DUCTS ARE IN
 A CONDITIONED SPACE, MECHANICAL PLANS SHOW THEM IN THE
 ATTIC. PLEASE CORRECT ENERGY CALCULATIONS.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) NEED TO SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS ON
 MECHANICAL PLANS.
  
 4) SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN, DUCT NEEDS
 TO BE SIZED.
  
 5) SHOW ON MECHANICAL PLAN HOW RETURN AIR IS GETTING
 BACK TO THE AIR HANDLER UNIT.
  
 6) ALL INFORMATION, DRAWINGS, MECHANICAL PLANS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.