Plan Review Notes For Permit 07070363 |
Permit Number |
07070363 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-18 15:28:56 | *** DENIED *** | | 1) ENERGY CALCULATIONS SHOW THE RETURN AIR DUCTS ARE IN | | A CONDITIONED SPACE, MECHANICAL PLANS SHOW THEM IN THE | | ATTIC. PLEASE CORRECT ENERGY CALCULATIONS. | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 3) NEED TO SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS ON | | MECHANICAL PLANS. | | | | 4) SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN, DUCT NEEDS | | TO BE SIZED. | | | | 5) SHOW ON MECHANICAL PLAN HOW RETURN AIR IS GETTING | | BACK TO THE AIR HANDLER UNIT. | | | | 6) ALL INFORMATION, DRAWINGS, MECHANICAL PLANS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | FOR THE DESIGN. PER FBC 104.2.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|