2007-07-26 10:40:45 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3)FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 4) SPECIFY THE TRUSS BOTTOM CORD LIVE LOAD ON THE |
| PLANS. TABLE R301.5 REQUIRES 10 PSF FOR ATTICS WITHOUT |
| STORRAGE AND 20 PSF FOR ATTICS WITH STORAGE. |
| |
| 5) THE WALL SECTION ON A1.2 SPECIFIES 8" MINIMUM ABOVE |
| GRADE. WITH THE 18" FOOTER, THIS LEAVES 10" FROM GRADE |
| TO THE BOTTOM OF THE FOOTER. SEE FBC R403.1.4 MINIMUM |
| DEPTH. |
| ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 |
| INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| |
| 6) SPECIFY ALL NEW WINDOW AND DOOR TYPES AND SIZES ON |
| THE PLANS. |
| |
| 7) AT LEAST ONE WINDOW IN EVERY SLEEPING ROOM IS |
| REQUIRED TO COMPLY WITH R310.1 FOR EMERGENCY ESCAPE AND |
| RESCUE. |
| |
| 8) SHOW COMPLIANCE WITH THE FOLLOWING: |
| 311.4.1 EXIT DOOR REQUIRED. |
| NOT LESS THAN ONE EXIT DOOR CONFORMING TO THIS SECTION |
| SHALL BE PROVIDED FOR EACH DWELLING UNIT. THE REQUIRED |
| EXIT DOOR SHALL PROVIDE FOR DIRECT ACCESS FROM THE |
| HABITABLE PORTIONS OF THE DWELLING TO THE EXTERIOR |
| WITHOUT REQUIRING TRAVEL THROUGH A GARAGE. ACCESS TO |
| HABITABLE LEVELS NOT HAVING AN EXIT IN ACCORDANCE WITH |
| THIS SECTION SHALL BE BY A RAMP IN ACCORDANCE WITH |
| SECTION R311.6 OR A STAIRWAY IN ACCORDANCE WITH SECTION |
| R311.5 .SHOWR311.4.2 DOOR TYPE AND SIZE. |
| THE REQUIRED EXIT DOOR SHALL BE A SIDE-HINGED DOOR NOT |
| LESS THAN 3 FEET (914 MM) IN WIDTH AND 6 FEET 8 INCHES |
| (2032 MM) IN HEIGHT. OTHER DOORS SHALL NOT BE REQUIRED |
| TO COMPLY WITH THESE MINIMUM DIMENSIONS. ONE LEAF OF |
| DOUBLE DOORS MUST COMPLY. |
| |
| 9) SHOW COMPLIANCE WITH R322.1, WHICH REQUIRES AT LEAST |
| ONE BATHROOM TO HAVE A DOOR WITH A 29" CLEAR OPENING, |
| MEASURED FROM THE FACE OF THE DOOR TO THE OPPOSITE STOP |
| WITH THE DOOR OPEN 90 DEGREES. |
| |
| 10) PROVIDE DETAILS FOR THE CONCRETE BEAM AT THE |
| COVERED REAR PORCH AND ITS REINFORMENT. |
| |
| 11) PROVIDE DETAILS FOR THE TWO COLUMNS SUPPORTING THE |
| CONCRETE BEAM AT THE REAR PORCH. |
| |
| 12) PROVIDE DETAILS FOR THE ARCH OPENING AT THE FRONT |
| ENTRY. |
| |
| 13) THE WALL SECTION ON A1.2 SPECIFIES A 3:12 ROOF |
| SLOPE AND THE NOTES ON SHEET A1.4 SPECIFY A 5:12 SLOPE. |
| PLEASE CORRECT. NOTE: FBC R905.2.7 REQUIRES ROOFS WITH |
| SOPES LESS THAN 4:12 TO HAVE TWO LAYERS OF |
| UNDERLAYMENT. |
| |
| 14) REVISE THE ROOF SHEATHING FASTENING NOTES ON A1.3 |
| TO COMPLY WITH R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC |
| RESIDENTIAL CODE.WHICH REQUIRES WOOD STRUCTURAL PANEL |
| SHEATHING TO BE FASTENED TO ROOF FRAMING WITH 8D |
| RING-SHANK NAILS IN ALL ROOF ZONES AND THE SPACING OF |
| RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN |
| NAILING ZONE 3. |
| |
| 15) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| THE (2) 2X12 RIM BEAMS TO THE EXISTING STRUCTURE AND |
| THE NEW CONC. COLUMNS AT THE ENTRY. CLARIFY WHERE THE |
| META 16 CONNECTORS WILL BE USED. SPECIFY THE NUMBER AND |
| TYPE OF NAILS TO BE USED WITH THE META 16 CONNECTORS. |
| SEE THE ENTRY SECTION ON A1.1. |
| |
| 16) ON THE ROOF PLAN ON A1.3 CLARIFY THAT THE MTS 12 |
| CONNECTOR IS REQUIRED TO HAVE 7 NAILS AT EACH END OF |
| THE STRAP FOR A TOTAL OF 14. |
| |
| 17) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| THE LARGE TRUSSES AT THE REAR ADDITION TO THE EXISTING |
| WALL AND TO THE EXISTING TRUSSES. |
| |
| 18) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS. |
| IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED |
| TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) |
| AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR |
| GREATER. |
| THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22 |
| INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE |
| LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE |
| LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED |
| HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME |
| POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3 |
| FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| LOCATED IN ATTICS. |
| |
| 19) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| CALCULATIONS PER FBC CHAPTER 13. |
| |
| 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. |
| |
| 21)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 22) SUBMIT PRODUCT APPROVAL FOR THE ROOFING MATERIAL, |
| THE EXTERIOR DOOR TO THE LAUNDRY ROOM, THE INSWING |
| FRENCH DOOR AT THE ENTRY (THE ONES THAT WERE SUBMITTED |
| ARE FOR OUTSWING DOORS) AND THE TRUSS ANCHORS. |
| |
| 23) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS THAT |
| ARE REQUIRED AT NON-IMPACT RATED FRENCH DOORS. SPECIFY |
| THE MOUNT TYPE, THE FASTENERS, AND THE FASTENER |
| SPACING. THESE ITEMS CAN BE CIRCLED ON THE NOA. |
| |
| 24) THE NOA SUBMITTED FOR THE TRACO IMPACT RATED SINGLE |
| HUNG WINDOWS HAS BEEN REVISED BY NOA NO. 05-0930.03. |
| PLEASE SUBMIT THE NEW NOA. |
| |
| 25) ARE THE WINDOWS THAT ARE SHOWN ON THE FLOOR PLAN |
| BETWEEN THE GUEST BATH / DEN AND THE MASTER BEDROOM TO |
| REMAIN IN THE EXISTING WALL? |
| |
| 26) THE VALUE OF THE WORK HAS BEEN INCREASED BASED ON |
| THE ICC BUILDING VALUATION DATA. ADDITIONAL PERMIT FEES |
| OF $937.77 ARE DUE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |