Plan Review Notes
Plan Review Notes For Permit 07070363
Permit Number 07070363
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-26 10:40:45DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4) SPECIFY THE TRUSS BOTTOM CORD LIVE LOAD ON THE
 PLANS. TABLE R301.5 REQUIRES 10 PSF FOR ATTICS WITHOUT
 STORRAGE AND 20 PSF FOR ATTICS WITH STORAGE.
  
 5) THE WALL SECTION ON A1.2 SPECIFIES 8" MINIMUM ABOVE
 GRADE. WITH THE 18" FOOTER, THIS LEAVES 10" FROM GRADE
 TO THE BOTTOM OF THE FOOTER. SEE FBC R403.1.4 MINIMUM
 DEPTH.
 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 6) SPECIFY ALL NEW WINDOW AND DOOR TYPES AND SIZES ON
 THE PLANS.
  
 7) AT LEAST ONE WINDOW IN EVERY SLEEPING ROOM IS
 REQUIRED TO COMPLY WITH R310.1 FOR EMERGENCY ESCAPE AND
 RESCUE.
  
 8) SHOW COMPLIANCE WITH THE FOLLOWING:
 311.4.1 EXIT DOOR REQUIRED.
 NOT LESS THAN ONE EXIT DOOR CONFORMING TO THIS SECTION
 SHALL BE PROVIDED FOR EACH DWELLING UNIT. THE REQUIRED
 EXIT DOOR SHALL PROVIDE FOR DIRECT ACCESS FROM THE
 HABITABLE PORTIONS OF THE DWELLING TO THE EXTERIOR
 WITHOUT REQUIRING TRAVEL THROUGH A GARAGE. ACCESS TO
 HABITABLE LEVELS NOT HAVING AN EXIT IN ACCORDANCE WITH
 THIS SECTION SHALL BE BY A RAMP IN ACCORDANCE WITH
 SECTION R311.6 OR A STAIRWAY IN ACCORDANCE WITH SECTION
 R311.5 .SHOWR311.4.2 DOOR TYPE AND SIZE.
 THE REQUIRED EXIT DOOR SHALL BE A SIDE-HINGED DOOR NOT
 LESS THAN 3 FEET (914 MM) IN WIDTH AND 6 FEET 8 INCHES
 (2032 MM) IN HEIGHT. OTHER DOORS SHALL NOT BE REQUIRED
 TO COMPLY WITH THESE MINIMUM DIMENSIONS. ONE LEAF OF
 DOUBLE DOORS MUST COMPLY.
  
 9) SHOW COMPLIANCE WITH R322.1, WHICH REQUIRES AT LEAST
 ONE BATHROOM TO HAVE A DOOR WITH A 29" CLEAR OPENING,
 MEASURED FROM THE FACE OF THE DOOR TO THE OPPOSITE STOP
 WITH THE DOOR OPEN 90 DEGREES.
  
 10) PROVIDE DETAILS FOR THE CONCRETE BEAM AT THE
 COVERED REAR PORCH AND ITS REINFORMENT.
  
 11) PROVIDE DETAILS FOR THE TWO COLUMNS SUPPORTING THE
 CONCRETE BEAM AT THE REAR PORCH.
  
 12) PROVIDE DETAILS FOR THE ARCH OPENING AT THE FRONT
 ENTRY.
  
 13) THE WALL SECTION ON A1.2 SPECIFIES A 3:12 ROOF
 SLOPE AND THE NOTES ON SHEET A1.4 SPECIFY A 5:12 SLOPE.
 PLEASE CORRECT. NOTE: FBC R905.2.7 REQUIRES ROOFS WITH
 SOPES LESS THAN 4:12 TO HAVE TWO LAYERS OF
 UNDERLAYMENT.
  
 14) REVISE THE ROOF SHEATHING FASTENING NOTES ON A1.3
 TO COMPLY WITH R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE.WHICH REQUIRES WOOD STRUCTURAL PANEL
 SHEATHING TO BE FASTENED TO ROOF FRAMING WITH 8D
 RING-SHANK NAILS IN ALL ROOF ZONES AND THE SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3.
  
 15) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE (2) 2X12 RIM BEAMS TO THE EXISTING STRUCTURE AND
 THE NEW CONC. COLUMNS AT THE ENTRY. CLARIFY WHERE THE
 META 16 CONNECTORS WILL BE USED. SPECIFY THE NUMBER AND
 TYPE OF NAILS TO BE USED WITH THE META 16 CONNECTORS.
 SEE THE ENTRY SECTION ON A1.1.
  
 16) ON THE ROOF PLAN ON A1.3 CLARIFY THAT THE MTS 12
 CONNECTOR IS REQUIRED TO HAVE 7 NAILS AT EACH END OF
 THE STRAP FOR A TOTAL OF 14.
  
 17) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE LARGE TRUSSES AT THE REAR ADDITION TO THE EXISTING
 WALL AND TO THE EXISTING TRUSSES.
  
 18) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 19) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATIONS PER FBC CHAPTER 13.
  
 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 21)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 22) SUBMIT PRODUCT APPROVAL FOR THE ROOFING MATERIAL,
 THE EXTERIOR DOOR TO THE LAUNDRY ROOM, THE INSWING
 FRENCH DOOR AT THE ENTRY (THE ONES THAT WERE SUBMITTED
 ARE FOR OUTSWING DOORS) AND THE TRUSS ANCHORS.
  
 23) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS THAT
 ARE REQUIRED AT NON-IMPACT RATED FRENCH DOORS. SPECIFY
 THE MOUNT TYPE, THE FASTENERS, AND THE FASTENER
 SPACING. THESE ITEMS CAN BE CIRCLED ON THE NOA.
  
 24) THE NOA SUBMITTED FOR THE TRACO IMPACT RATED SINGLE
 HUNG WINDOWS HAS BEEN REVISED BY NOA NO. 05-0930.03.
 PLEASE SUBMIT THE NEW NOA.
  
 25) ARE THE WINDOWS THAT ARE SHOWN ON THE FLOOR PLAN
 BETWEEN THE GUEST BATH / DEN AND THE MASTER BEDROOM TO
 REMAIN IN THE EXISTING WALL?
  
 26) THE VALUE OF THE WORK HAS BEEN INCREASED BASED ON
 THE ICC BUILDING VALUATION DATA. ADDITIONAL PERMIT FEES
 OF $937.77 ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved