Plan Review Notes
Plan Review Notes For Permit 07070269
Permit Number 07070269
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-06 11:49:49*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.SPECIFY WALL RATING BETWEEN GARAGE AND LIVING
 AREA.
  
 4.ON SHEET A-5, AMEND VERBAGE TO READ SMOKE ALARMS
 (SA) INSTEAD OF SMOKE DETECTORS (SD).BE ADVISED THAT
 SMOKE DETECTORS ARE TIED INTO A FIRE ALARM SYSTEM FOR
 THE BUILDING, WHEREAS SMOKE ALARMS ALERT THE
 OCCUPANT(S) OF THE DWELLING UNIT.
  
 5.ON SHEET A-7 INCLUDE THE APPROPIATE DIRECTION WITH
 THE FRONT, REAR, LEFT SIDE, AND RIGHT SIDE EXTERIOR
 ELEVATIONS FOR CORRELATION.
  
 6.ON THE APPROPIATE EXTERIOR ELEVATION FRONTING LILAC
 COURT, POST THE NUMERICAL ADDRESS ON THE BUILDING.AS
 PER WEST PALM BEACH CODE, THOSE NUMBERS (515) SHALL BE
 NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
 THE UNIT CHARACTERS (NUMBERS OR LETTERS) SHALL BE NO
 LESS THAN 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722