2007-08-30 14:27:29 
  
 DENIED
  
 THIS REVIEW IS BASED PERMIT APPLICATIONS FOR FEE SIMPLE
 TOWNHOUSES
  
 1)PLEASE SET UP MEETING WITH THE PLANNING AND ZONING
 DEPARTMENT FOR SEPARATION OF PROPERTY AND WITH
 ADDRESSING TO ARRANGE SEPARATE ADDRESSES FOR EACH
 PROPERTY
  
 2)THREE SEPARATE AND COMPLETE PERMIT APPLICATIONS ARE
 REQUIRED FOR EACH TOWNHOUSE, EACH SHALL CONTAIN THE
 INDIVIDUAL ADDRESS FOR THE UNIT AND ALL PERTINENT
 INFORMATION ( NOTICE OF COMMENCEMENT, PRODUCT
 APPROVALS, ENERGY CALC'S, ETC.)
  
 3)THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES PER 108.3 FBC*
 ********VALUE FOR EACH UNIT BASED ON THE BVD FROM THE
 ICC AT THE TIME OF PERMIT APPLICATION IS $186,546.00
 PER UNIT******
  
 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES. THE FEES ARE DUE
 ON EACH UNIT BASED ON 1,943 SQ. FT.
  
 5)DUE TO PERMIT EXPIRATION AND RE-APPLICATION THE
 DESIGN DATA AND GENERAL INFORMATION SHALL COMPLY WITH
 THE 2004 FBC W/ 2006 AMENDMENTS
  
 6)FASTENER SCHEDULE TO COMPLY WITH THE NEW REVISION
 TO THE 2004 FBC RES. R803.2.3.1 REQUIRES 8D RING SHANK
 NAILS AT 6" O/C EDGES AND FIELD AND 4" O/C EDGES AND
 FIELD IN ZONE 3
  
 7)THE FIRE RATED SYSTEM CHOSEN ON A8 NO 8-2-11W FROM
 RINKER SHOWS BLOCK FURRED WITH METAL CHANNEL AND 1/2"
 DRYWALL APPLIED TO BOTH SIDES, THIS DETAIL MUST
 CONTINUE FROM FLOOR TO UNDERSIDE OF ROOF DECK (PLYWOOD
 SHEATHING) PLEASE NOTE THAT THE SYSTEM SEEMS TO STOP AT
 BOTTOM OF TRUSSES ON SECTION L/8.
  
 8)PLEASE SEE THAT SECTION L/8 IS VERY CONFUSING IT
 SHOWS STUCCO, 2X2 FURRING AND 1-5/8" METAL STUDS. IT
 SHOULD SHOW THE FIRE RATING DETAIL AND THE CHOSEN
 FURRING DETAIL FOR ELECTRICAL/PLUMBING TO KEEP THE FIRE
 RATING INTACT.
  
 9)THE WINDOWS PROVIDED FOR THE MASTER BEDROOM SH34 DO
 NOT MEET THE MINIMUM REQUIRED VERTICAL OPENING OF 24"
 PER R310.1.2 FBC RES.
  
 10)THE SHUTTER PRODUCT APPROVAL IS NO LONGER VALID, A
 NEW DRAWING # 06-368 UNDER FL# 7030 SEEMS TO BE THE
 SAME PANEL TYPE WITH CHANGES ONLY FOR THE UPDATED ASCE
 7-02. ALSO THE SHUTTER SCHEDULE WILL BE NEED TO BE
 SEPARATED INTO THE INDIVIDUAL UNITS FOR EACH PERMIT.
  
 11)THE ROOFING PRODUCT APPROVAL IS ALSO UPDATED FL#
 183-R2 WITH A NEW MIAMI-DADE REPORT # 05-1115.11
  
 12)THE SIMONTON WINDOW PRODUCT APPROVAL FOR THE
 500-500 STORMBREAKER SLIDING GLASS DOOR IS NO LONGER
 APPROVED ON THE STATE SITE AND THE MIAMI-DADE FILE HAS
 BEEN CLOSED.
  
 13)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  