Plan Review Notes
Plan Review Notes For Permit 07070235
Permit Number 07070235
Review Stop M
Sequence Number 2
Notes
Date Text
2007-09-24 15:37:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 7-17-07 #1. BUILDING PLANS
 TITLE BLOCK NEEDS TO ALSO SHOW THE PRINTED NAME OF THE
 PERSON WHO SEALED THEM (RODNEY N. GREEN), SEE FAC
 61G1-16.004.
  
 2) AS NOTED IN LAST REVIEW 7-17-07 #1. BUILDING PLANS
 TITLE BLOCK NEEDS TO ALSO SHOW RNGA ARCHITECTURE INC.
 FIRM LICENSE NUMBER (AA26000717), SEE FAC 61G1-16.004.
  
 3) AS NOTED IN LAST REVIEW 7-17-07 #4. THE MECHANICAL
 PLANS NEED TO SHOW THE AN EXHAUST FAN IN THE MASTER
 BATHROOM SHOWER AND TUB AREA, SEE FBC/R R303.3.
  
 5) AS NOTED IN LAST REVIEW 7-17-07 #7. THE MECHANICAL
 PLANS NEED THE PRINTED NAME OF THE PERSON RESPONSIBLE
 FOR THE DESIGN ON THEM ALSO, SEE W.P.B. AMEND.
 106.1.3.
  
 6) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLANS SHOWING
 MISSING DUCT WORK (FLEX), PLEASE CORRECT.
  
 7)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]