2007-09-24 13:35:30 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING
 CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC
 AS
 AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW7/17/07.
  
 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM,
 ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL
 EQUIPMENT ON THE PLAN. *THE METER AND DISCONNECT ARE
 NOT SHOWN ON THIS RESUBMITTAL EITHER. 106.1.1 FBC.
  
 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH
 210.52(B)(1), NOTE FOR PANEL SCHEDULE.* THEE PANEL
 SCHEDULE HAS A 15 AMP BREAKER, MUST BE A 20 AMP CIRCUIT
 TO COMPLY.
  
 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN
 VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO
 THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT. *
 NOW THE ?CLOSET? IS RENAMED ?STORAGE?, SEE 422.17 TO
 DETERMINE IF THIS UNIT NEEDS TO BE WALLED OFF FROM
 ITEMS INTENDED TO BE STORED IN THIS ROOM.
  
 THESE ARE NEW COMMENTS FOR THIS REVIEW GENERATED BY THE
 PANEL SCHEDULE BEING ADDED TO THE PLAN.
  
 1} SEE COMMENT #8 ABOVE.
  
 2} THERE IS ONLY ONE SMALL APPLIANCE CIRCUIT IN THE
 PANEL SCHEDULE, PER 210.11(C)(1), A MINIMUM OF TWO ARE
 REQUIRED.
  
 3} BATHROOM CIRCUITS ARE REQUIRED TO BE 20 AMP PER
 210.11(C)(3) ONLY THE MASTER BATH IS LISTED IN THE
 SCHEDULE, AND IT HAS A 15 AMP BREAKER.
  
 4} THE NOTE FOR PANEL ?A? ON THE RISER DIAGRAM READS
 ?MAIN METER?, CLARIFY IF THIS IS A METER MAIN
 COMBINATION PIECE OF SERVICE EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718