2007-07-17 16:49:48 | *** DENIED *** |
| 1) SEE BUILDING PLANS, INFORMATION MISSING IN TITLE |
| BLOCK (FIRM LIC. NO., FIRM PHONE NO., PERSON SEALED |
| PLANS PRINTED NAME) FOR ARCHITECT SEE FAC 61G1-16.004 |
| TITLE BLOCK. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" |
| SEE CITY WPB AMEND. 106.1.1). |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. |
| |
| 2) ENERGY CALCULATIONS LINE 15 IS TAKING CREDIT FOR |
| CEILING FANS. CEILING FANS ARE NOT IN THE TWO EXISTING |
| BEDROOMS, FAMILY ROOM, OR THE LIVING ROOM. PER 2004 FBC |
| 13-607.2.A.3.1 CEILING FAN CREDIT MAY BE TAKEN IF ONE |
| OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE |
| BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED |
| IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY |
| ROOMS, OR GREAT ROOMS). PLEASE CORRECT. |
| |
| 3) THE BATHROOM BETWEEN THE TWO EXISTING BEDROOMS WILL |
| NEED AN EXHAUST FAN, SEE 2004 FBC/R R303.3. |
| |
| 4) THE MASTER BATHROOM SHOWER AREA WILL NEED AN EXHAUST |
| FAN, SEE 2004 FBC/R R303.3. |
| |
| 5) SHOW CLOTHES DRYER VENT AND ALL BATHROOM EXHAUST |
| FANS ON MECHANICAL PLANS. |
| |
| 6) BUILDING AND ELECTRICAL PLANS SHOW THE AIR HANDLER |
| IN A CLOSET BUT THE MECHANICAL PLANS SHOW THE AIR |
| HANDLER IN THE GARAGE, THE TWO MUST COINCIDE PLEASE |
| CORRECT. |
| |
| 7) ALL INFORMATION, DRAWINGS (MECHANICAL PLANS), |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER |
| FBC 104.2.1 . |
| |