2007-07-17 13:53:59 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL |
| INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG |
| WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA |
| ADMINISTRATIVE CODE. |
| |
| 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL |
| SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO |
| BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 |
| NEC 2005. SEE 220.80 2005 NEC. SEE SMALL APPLIANCE AN |
| AHU. |
| |
| 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| CHANGE. |
| |
| 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM, |
| ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL |
| EQUIPMENT ON THE PLAN. |
| |
| 5} PROVIDE PANEL SCHEDULES PER 408.4, NEC,CIRCUIT |
| DIRECTORY OR CIRCUIT IDENTIFICATION |
| EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| DISTINGUISHED FROM ALL OTHERS. |
| |
| 6} THE KITCHEN PENINSULAR RECEPTACLE SPACING MUST |
| COMPLY WITH 210.52(C)(3). |
| |
| 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1), |
| SEE PROPOSED FAMILY ROOM. |
| |
| 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH |
| 210.52(B)(1), NOTE FOR PANEL SCHEDULE. |
| |
| 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN |
| VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO |
| THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT. |
| |
| NOTE: IF METAL STUDS ARE USED THEY MUST COMPLY WITH |
| 2704.1, 2004 FBC: METAL FRAMING MEMBERS SHALL BE BONDED |
| TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT |
| THAT MAY ENERGIZE THE FRAMING. PLEASE SEE ARTICLE.AND |
| NOTE ON PLAN. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |