 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005. SEE 220.80 2005 NEC. SEE SMALL APPLIANCE AN
 AHU.
  
 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM,
 ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL
 EQUIPMENT ON THE PLAN.
  
 5} PROVIDE PANEL SCHEDULES PER 408.4, NEC,CIRCUIT
 DIRECTORY OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 6} THE KITCHEN PENINSULAR RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(C)(3).
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1),
 SEE PROPOSED FAMILY ROOM.
  
 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH
 210.52(B)(1), NOTE FOR PANEL SCHEDULE.
  
 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN
 VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO
 THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT.
  
 NOTE: IF METAL STUDS ARE USED THEY MUST COMPLY WITH
 2704.1, 2004 FBC: METAL FRAMING MEMBERS SHALL BE BONDED
 TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT
 THAT MAY ENERGIZE THE FRAMING. PLEASE SEE ARTICLE.AND
 NOTE ON PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER