Plan Review Notes
Plan Review Notes For Permit 07070220
Permit Number 07070220
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-10 12:47:51*** REDLINED***
  
 ** PERMIT APPLICATION WAS NOT RESUBMITTED WITH PLANS.
 SPOKE TO FRANK FROM CATALFUMO, WILL BRING IN NEW
 APPLICATION.
  
  
 1) ELECTRICAL SHEET SUBMITTED FOR UNDERGROUND GROUNDING
 ELECTRODE SYSTEM ONLY.
  
 2) REDLINED ADDRESS ON ELECTRICAL SHEETS TITLE BLOCKS
 AS SHEETS DO NOT CONTAIN ADDRESS AS REQUIRED.
  
 3) CIVIL AND S-SHEETS ARE FOR FPL DUCT BANK AND THEIR
 REQUIREMENTS WHICH ARE NOT BASED ON ANY NEC
 REQUIREMENTS. (NOT REVIEW FOR MIN CODE).
  
 4) THE UNDERGROUND CONDUITS FOR BUILDING'S ELECTRICAL
 SERVICE AND OTHER ELECTRICAL EQUIPMENT WHICH IS PART OF
 THE MAIN STRUCURE IS NOT PART OF THESE PLANS OR
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717