Plan Review Notes
Plan Review Notes For Permit 07070220
Permit Number 07070220
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-31 14:11:39BUILDING PLAN REVIEW
 PERMIT: 07070220
 ADD: 500 BANYAN BLVD
 CONT: CATALFUMO
 TEL: (561)307-4746
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) )OF THE UTILTY SIGN OFF WE ARE MISSING THE WATER
 DEPARTMENT OR UTILITIES ENGINEERING DEPARTMENT. SHEET
 C-9 DOES INDICATE A 14' ALLEYWAY BETWEEN LOT1 AND LOT
 10, A COPY OF THE UNITY OF TITLE IS IN HAND. PLEASE
 UPDATE SHOWING THE ABANDOMENT OF THE ALLEYWAY AND THEN
 THE SIGN OFF FROM ENGINEERING AND UTILITIES. SHEET
 S1-1.0INDICATES THERE WILL BE AN FPL DUCTBANK BENEATH
 THE BUILDING EAST TO WEST PLEASE PROVIDE THE RECORDED
 UTILITY EASEMENT FOR THIS AREA AS WELL AS FOR THE FPL
 VAULT.
  
 3) SHEETLS0.0PLEASE CORRECT THE ADDRESS TO 500
 BANYAN.
  
 4) NOTE CORRECT FOR BUILDING PLAN LS0.0 FPL VAULT 3HR
 WALL PLANS INDICATE 90 MINUTE DOORS PLEASE SEE TABLE
 715.3 3HR WALLS/ 3 HR OPENING PROTECTIVES.
  
 5)S1-1.0 INDICATES THE USE OF 16" AUGER PILE WHERE AS
 THE SOILS REPORTS DO NOT REFLECT USING SUCH A SYSTEM.
 PLEASE PROVIDE THE GEOENGINEERS CALCULATIONS FOR DEPTH
 OF PILE.
  
 6) SOILS REPORTS SUBMITTED ARE COPIES NOT ORIGINAL
 SIGNED AND SEALED DOCUMENTS. NOTE THIS WILL BE A
 THRESHOLD BUILDING REQUIRING THREE DOCUMENTS TO BE
 SUBMITTED.
  
 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA STATUTES
 TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561) 805-6711 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 8) S2-4.0 VS DUCT BANK WHICH SYSTEM WILL BE INSTALLED
 FIRST,DUCT BANK, VIBROFLOTATION OR THE FOUNDATION SEE
 DETAIL# 8.IF THE DUCT BANK IS PLACED AFTER THE FOOTERS
 THE SOILS NATURAL REPOSE WILLUNDERMINE THE
 FOUNDATION.
  
 9)105.13. SPECIAL FOUNDATION PERMIT.WHEN APPLICATION
 FOR A PERMIT TO ERECT OR ENLARGE A BUILDING HAS BEEN
 FILED, & PENDING ISSURANCE OF SUCH PERMIT, THE BUILDING
 OFFICIAL MAY, AT HIS/ HER DISCRETION, ISSUE A SPECIAL
 PERMIT FOR THE FOUNDATION ONLY, UPON WRITTEN REQUEST OF
 THE OWNER AND CONTRACTOR. THE HOLDER OF SUCH A SPECIAL
 PERMIT IS PROCEEDING AT HIS OR HER OWN RISK AND WITHOUT
 ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  