Plan Review Notes For Permit 07070214 |
Permit Number |
07070214 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-08-31 14:57:36 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2004 | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1.ADDRESSED. | | | | 2.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC | | R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C | | HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC | | R301.2.1.4. | | | | PROVIDE DIMENSIONS ON THE FLOOR PLAN, DISTANCE FROM | | CORNER TO EDGE OF WINDOW, FOR OPENINGS NEAR THE CORNER. | | NUMBER THE OPENINGS TO CORRELATE WITH THE INSTALLATION | | SCHEDULE.THE OPENING 48X49, IF IN ZONE 5, HAS A | | DESIGN PRESSURE REQUIREMENT OF -57.11. | | | | 3.SEE SHEET14A; A FACTOR OF .5 REQURED FOR ANCHOR | | SPACING WITH EDGE DISTANCE OF 2". | | | | 2ND REVIEW; THIS WAS ADDRESSED BY CHANGING THE EDGE | | DISTANCE TO 3".THIS REQUIRES A FACTOR OF .86. | | | | 3RD REVIEW; IT APPEARS THAT YOU ARE READING THE | | COMMENTS FROM REVIEW #1.PLEASE SEE ABOVE AND REVIEW | | #2. | | | | NEW COMMENT: | | | | 4.)SHUTTER CONNECTION MOUNTING TYPE SHOULD BE A | | THROUGH L, NOT TAPCON.PLEASE REVISE. | | |
|