2007-08-31 14:57:36****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.ADDRESSED.
  
 2.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC
 R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C
 HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
 PROVIDE DIMENSIONS ON THE FLOOR PLAN, DISTANCE FROM
 CORNER TO EDGE OF WINDOW, FOR OPENINGS NEAR THE CORNER.
 NUMBER THE OPENINGS TO CORRELATE WITH THE INSTALLATION
 SCHEDULE.THE OPENING 48X49, IF IN ZONE 5, HAS A
 DESIGN PRESSURE REQUIREMENT OF -57.11.
  
 3.SEE SHEET14A; A FACTOR OF .5 REQURED FOR ANCHOR
 SPACING WITH EDGE DISTANCE OF 2".
  
 2ND REVIEW; THIS WAS ADDRESSED BY CHANGING THE EDGE
 DISTANCE TO 3".THIS REQUIRES A FACTOR OF .86.
  
 3RD REVIEW; IT APPEARS THAT YOU ARE READING THE
 COMMENTS FROM REVIEW #1.PLEASE SEE ABOVE AND REVIEW
 #2.
  
 NEW COMMENT:
  
 4.)SHUTTER CONNECTION MOUNTING TYPE SHOULD BE A
 THROUGH L, NOT TAPCON.PLEASE REVISE.
  