Plan Review Notes
Plan Review Notes For Permit 07070208
Permit Number 07070208
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-25 17:57:23DENIED BY BUILDING
  
 1)SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE REQUIRES ROOF SHEATHING TO BE FASTENED
 WITH 8D RING SHANK NAILS IN ALL ROOF ZONES. FASTENER
 SPACING IS REQUIRED TO BE 4" OC IN ROOF ZONE 3. PLEASE
 REVISE THE NOTES ON SHEET 2.
  
 2) SAFETY GLAZING IS REQUIRED IN THE MASTER BATHROOM
 WINDOW. PLEASE CLARIFY THAT T. G. IS AN ABBREVIATION
 FOR TEMPERED GLASS. THE ABBREVEATION TEMP. IS TYPICALLY
 USED TO DENOTE TEMPERED GLASS.
  
 3) THE ENERGY CALULATION FORM THAT WAS SUBMITTED HAS
 BEEN REVISED BY THE 2006 REVISIONS TO THE 2004 FBC. THE
 CURRENT FORM IS 600C-04R WHICH IS TWO SIDED. I HAVE
 ATTACHED A COPY OF IT TO THE OLD FORMS. THE OWNER/AGENT
 IS REQUIRED TO SIGN THE FORM. THE OVERHANG OF 2'
 SPECIFIED ON THE FORM DOES NOT CONCUR WITH THE OVERHANG
 OF 1'-6"SPECIFIED ON THE WALL SECTION ON SHEET 2 OF
 THE PLANS. PLEASE CORRECT.
  
 4)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE ROOFING MATERIAL.
  
 6) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 STORM PANELS HAS PARTS THAT ARE NOT LEGIBLE. SUBMIT
 CLEAR LEGIBLE COPIES.
  
 7) SPECIFY THE MOUNTING INSTALLATION, TYPE OF FASTENER
 AND FASTENER SPACING FOR THE STORM PANELS. THIS CAN BE
 DONE BY CIRCLING THE APPROPRIATE ITEMS ON THE PRODUCT
 APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714