2007-08-07 13:12:31 | SWIMMING POOL BUILDING REVIEW FIRST CHECKLIST (REVIEW |
| DONE UNDER FBC 2004 WITH 2006 REVISIONS): |
| |
| 1- NEED TO SUBMIT TWO COMPLETE AND EQUAL SETS OF |
| DRAWINGS AS REQUIRED BY SEC. 106.1 CITY AMENDMENTS TO |
| FBC 2004.PLANS SUBMITTED DON'T MATCH, WERE SIGNED AND |
| SEALED ON DIFFERENT DATES AND ONE OF THEM HAS |
| HANDWRITTENREVISIONS.PLANS NEED TO MATCH AND |
| HANDWRITTEN INFORMATION IS NOT ALLOWED. ANY CHANGES |
| SHALL BE DONE ON ORIGINAL DRAWINGS. |
| |
| 2- SHEET 1 OF 1:POOL WAS DESIGNED USING THE 2001 |
| FLORIDA BUILDING CODE.CURRENT CODE IS THE FBC 2004 |
| AND 2004 FLORIDA RESIDENTIAL CODE.THIS IS A |
| RESIDENTIAL POOL, THEREFORE CORRECT CODE TO USEIS |
| CHAPTER 41 OF OF2004 FLORIDA RESIDENTIAL CODE. |
| ENGINEERING DESIGN SHALL BE DONE AS PER SEC. R4101.6. |
| REVISE ALL NOTES ON SHEET 1 THAT REFER TO FBC 2001 OR |
| SECTION 424 OF FLORIDA BUILDING CODE OF 2001. |
| |
| 3- POOL SPECIFICATIONS ON SHEET 1 DON'T MATCH DRAWINGS. |
| EG: SEE POOL DIMENSIONS AND VOLUME. REVISE AS REQUIRED |
| TO MATCH. |
| |
| 4- ENGINEER NEEDS TO USE CURRENT SEAL THAT READS |
| "LICENSE" INSTEAD OF "CERTIFICATE" AS REQUIRED BY THE |
| BOARD OF ENGINEERS. |
| |
| 5- CLEARLY IDENTIFY WHICH RESIDENTIAL SWIMMING BARRIER |
| IS GOING TO BE USED AS REQUIRED BY SEC. R4101.17 OF |
| 2004 FLORIDA RESIDENTIAL CODE. |
| NOTE: KEEP IN MIND THAT ONE BARRIER IS FROM THE HOUSE |
| TO THE POOL AND ANOTHER BARRIER REQUIRED IS FROM THE |
| OUTSIDE OF THE HOUSE. EG: ENTRANCE TO POOL FROM OUTSIDE |
| GATES. |
| |
| 6-POOL VALUE DECLARED ON THE PERMIT APPLICATION WAS |
| UPDATED TO $45,718, WHICH WAS THE CALCULATED VALUE USED |
| ON PREVIOUS PERMIT BEFORE IT WAS EXPIRED. OWES $418.50 |
| AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |