2007-08-07 13:12:31SWIMMING POOL BUILDING REVIEW FIRST CHECKLIST (REVIEW
 DONE UNDER FBC 2004 WITH 2006 REVISIONS):
  
 1- NEED TO SUBMIT TWO COMPLETE AND EQUAL SETS OF
 DRAWINGS AS REQUIRED BY SEC. 106.1 CITY AMENDMENTS TO
 FBC 2004.PLANS SUBMITTED DON'T MATCH, WERE SIGNED AND
 SEALED ON DIFFERENT DATES AND ONE OF THEM HAS
 HANDWRITTENREVISIONS.PLANS NEED TO MATCH AND
 HANDWRITTEN INFORMATION IS NOT ALLOWED. ANY CHANGES
 SHALL BE DONE ON ORIGINAL DRAWINGS.
  
 2- SHEET 1 OF 1:POOL WAS DESIGNED USING THE 2001
 FLORIDA BUILDING CODE.CURRENT CODE IS THE FBC 2004
 AND 2004 FLORIDA RESIDENTIAL CODE.THIS IS A
 RESIDENTIAL POOL, THEREFORE CORRECT CODE TO USEIS
 CHAPTER 41 OF OF2004 FLORIDA RESIDENTIAL CODE.
 ENGINEERING DESIGN SHALL BE DONE AS PER SEC. R4101.6.
 REVISE ALL NOTES ON SHEET 1 THAT REFER TO FBC 2001 OR
 SECTION 424 OF FLORIDA BUILDING CODE OF 2001.
  
 3- POOL SPECIFICATIONS ON SHEET 1 DON'T MATCH DRAWINGS.
 EG: SEE POOL DIMENSIONS AND VOLUME. REVISE AS REQUIRED
 TO MATCH.
  
 4- ENGINEER NEEDS TO USE CURRENT SEAL THAT READS
 "LICENSE" INSTEAD OF "CERTIFICATE" AS REQUIRED BY THE
 BOARD OF ENGINEERS.
  
 5- CLEARLY IDENTIFY WHICH RESIDENTIAL SWIMMING BARRIER
 IS GOING TO BE USED AS REQUIRED BY SEC. R4101.17 OF
 2004 FLORIDA RESIDENTIAL CODE.
 NOTE: KEEP IN MIND THAT ONE BARRIER IS FROM THE HOUSE
 TO THE POOL AND ANOTHER BARRIER REQUIRED IS FROM THE
 OUTSIDE OF THE HOUSE. EG: ENTRANCE TO POOL FROM OUTSIDE
 GATES.
  
 6-POOL VALUE DECLARED ON THE PERMIT APPLICATION WAS
 UPDATED TO $45,718, WHICH WAS THE CALCULATED VALUE USED
 ON PREVIOUS PERMIT BEFORE IT WAS EXPIRED. OWES $418.50
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
 [email protected]