2007-07-12 12:03:16-------------DENIED----------------
  
 FBC 2004 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 SEQUENCE OF OPERATIONS:
  
 1. PG.1: WHY DOES THE SEQUENCE FOR AHU-1 STATE THAT
 AHU-2 WILL BE COMMANDED "ON" DURING THE UNOCCUPIED MODE
 FOR AHU-1?
  
 2. PG.2: IS AHU-2 TO SHUT DOWN UPON SIGNAL FROM THE
 FIRE ALARM SYSTEM AS INDICATED ON M-510?
  
 3. PP.2 & 3 EF 1-2
 PART A: THE MOTORIZED DAMPERS ARE ASSOCIATED WITH
 LOUVERS L-5 AND L-6 AS SHOWN ON M-101, NOT L-4 AND L-5.
 PLEASE CORRECT. ALSO, L-7 AND L-8 DAMPERS ARE NOT
 MENTIONED IN THE SEQUENCE, BUT ARE SHOWN ON DRAWING 12.
 PLEASE COORDINATE SEQUENCE AND DRAWINGS.
  
 PART B: WHAT IS THE RELATIONSHIP BETWEEN THE MOTORIZED
 DAMPERS IN THE APPARATUS BAY AND EF-6, EF-7 AND EF-9?
 NOTE THAT ACCORDING TO THE SCHEDULE ON M-601, EF-7 AND
 EF-9 DO NOT EXIST. SHOULD THE FANS ASSOCIATED WITH THE
 DAMPERS BE EF-1 AND EF-2?
  
 4. PG.3 EXHAUST FAN INTERLOCKS: EF-1 IS NOT TO BE
 INTERLOCKED WITH AHU-1, EF-6 IS TO BE INTERLOCKED WITH
 AHU-1 AS SHOWN ON M-601. EF-9 DOES NOT EXIST AS SHOWN
 ON M-601 WHICH MEANS IT CAN NOT BE INTERLOCKED WITH
 AHU-3.
  
 5. DRAWING 11: FAN SCHEDULE ON M-601 INDICATES EF-9 IS
 NOT USED. PLEASE CLARIFY.
  
 6. DRAWING 12: WHERE ARE THE CONTROLS FOR L-5 AND L-6
 MOTORIZED DAMPERS? ALSO, L-7 ANDL-8 DAMPERS ARE NOT
 MENTIONED IN THE SEQUENCE OF OPERATIONS. PLEASE
 COORDINATE THE SEQUENCE WITH DRAWINGS.
  
 NOTE: SEQUENCE AND CONTROL DRAWINGS MAY HAVE BEEN
 DESIGNED BASED ON OUTDATED PLANS. THERE HAVE BEEN 3
 REVISIONS TO THE MECHANICAL PLANS SINCE THE PLANS
 PROVIDED WITH THIS APPLICATION (FOR REFERENCE) WERE
 ISSUED.
  