2007-07-20 13:04:38 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| 1. PLEASE SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY |
| ON THE RESUBMITTAL WITH THE FOLLOWING INFORMATION: |
| |
| A} THE CLEARLY MARKED PROPOSED LOCATION FOR |
| INSTALLATION OF GENERATOR. |
| |
| B} INDICATION OF ALL DIMENSIONS FROM PROPERTY LINES |
| AND DISTANCES FROM ADJACENT DWELLING STRUCTURES. |
| |
| C} INDICATION OF ANY EASEMENTS. PER CITY OF WEST PALM |
| BEACH ZONING LAND DEVELOPMENT REGULATIONS 94-303, THE |
| GENERATOR SHALL NOT EXTEND MORE THAN FOUR FEET INTO THE |
| REQUIRED SETBACK. CONTACT THE WPB ZONING DEPARTMENT FOR |
| DETAILS REGARDING SETBAKS. |
| |
| D} INDICATION THAT THE GENERATOR EXHAUST IS NOT |
| INSTALLED ANY CLOSER THAN TEN FEET FROM ANY OPENING |
| INTO THE DWELLING STRUCTURE. THIS INCLUDES DOORS |
| WINDOWS AND ATTIC VENTILATION OPENINGS. |
| |
| 2. PLEASE SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS/CUT SHEETS FOR THE GENERATOR TO VERIFY |
| THE BTU LOAD OF THE GENERATOR. PLEASE SUBMIT |
| INSTALLATION INSTRUCTIONS WITH MANUFACTURER SETBACK |
| RECOMMENDATIONS OF THE GENERATOR FROM STRUCTURES. |
| |
| 3. NOTE: PER FBC-2004 FUEL GAS TABLE 402.4(2) WITH A |
| 90' DEVELOPED LENGTH OF THE GAS SYSTEM THE GAS PIPING |
| TO THE GENERATOR NEEDS TO BE INCREASED TO 1" ON THE |
| RESUBMITTAL. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED AND |
| PROVIDE ONE COPY OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: ONLY ONE CORRECTED DRAWING IN RED INK FOR |
| REFERENCE FOR RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |