| PLEASE REPLY, IN WRITING OR ON THE PLAN, TO THE |
| FOLLOWING ARTICLES FROM THE 2005 NEC, WHICH MAY |
| APPLY.INDICATE SPACING TO THE RECEPTACLES FROM THE |
| OUTER EDGE OF THE PROPOSED WALL. |
| |
| 210.52(A) GENERAL PROVISIONS IN EVERY KITCHEN, FAMILY |
| ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN, |
| SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR |
| AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE |
| INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS |
| SPECIFIED IN 210.52(A)(1) THROUGH (A)(3). |
| (1) SPACING RECEPTACLES SHALL BE INSTALLED SO THAT NO |
| POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY |
| WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| OUTLET. |
| |
| DINING ROOMS MUST ALSO COMPLY WITH 210.52(B), SMALL |
| APPLIANCE RECEPTACLE REQUIREMENT. |
| |
| ALSO NOTE SECTION,. R313.1.1, FBC. ALTERATIONS, |
| REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. ALSO SEE |
| EXCEPTION. |
| |