2007-08-09 08:02:02 | 2004 FBC | | | | 1) THE ONLY ITEM LISTED IN THE DESCRIPTION OF WORK ON | | THE PERMIT APPLICATION THAT REQUIRES A PERMIT IS THE | | INTERIOR PARTITIONS. | | | | 2) OWNER BUILDERS ARE NOT ALLOWED TO ACT AS CONTRACTORS | | FOR GROUP R2 MULTIFAMILY RESIDENTIAL BUILDINGS. YOU | | WILL BE REQUIRED TO HIRE A LICENSED GENERAL CONTRACTOR | | TO CONSTRUCT THE INTERIOR PARTITIONS. | | | | 3) PLANS ARE REQUIRED TO BE DRAFTSMAN QUALITY DRAWN TO | | A MINIMUM OF 1/8 INCH SCALE. NO HANDWRITTEN NOTES IN | | PENCIL ARE ALLOWED ON THE PLANS. THE PLANS ARE REQUIRED | | TO BE CLEAR AND SUITABLE TO COPY FOR RECORD KEEPING | | PURPOSES.SEE FBC*106.1.3 CITY AMENDMENTS TO THE 2004 | | FBC. | | | | 4) FBC 717.5 DOES NOT ALLOW COMBUSTIBLES IN CONCEALED | | SPACES IN TYPE I OR II CONSTRUCTION. FBC 603.1 ALLOWS | | FIRE-RETARDANT-TREATED WOOD IN NONBEARING PARTITIONS | | WHERE FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. | | THEREFORE, THE 2X4 PT BASEPLATE IS REQUIRED TO BE | | FIRE-RETARDANT-TREATED WOOD. | | | | 5) PROVIDE A WALL SECTION OF THE INTERIOR PARTITION. | | SPECIFY STUD SPACING, ANCHOR TYPE AND SPACING THAT WILL | | BE USED TO ATTACH TOP AND BOTTOM OF WALLS TO EXISTING | | STRUCTURE, ETC. SEE FBC106.1.2. | | | | 6) ADDITIONAL PERMITS FOR ELECTRICAL MAY BE REQUIRED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | |
|