Plan Review Notes
Plan Review Notes For Permit 07070140
Permit Number 07070140
Review Stop M
Sequence Number 2
Notes
Date Text
2007-08-29 13:16:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A 13.40 SEER A/C
 SYSTEM, AND THE MECHANICAL PLANS ARE CALLING FOR A
 13.00 SEER. THE TWO MUST COINCIDE PLEASE CORRECT.
  
 2) COULD NOT FIND THE A/C SYSTEM MODEL #25HBR330 LISTED
 ON THE MECHANICAL PLANS IN THE ARI DIRECTORY OR ON THE
 CARRIER WEB SITE. PLEASE SUBMIT THE ARI REFERENCE
 NUMBER, ORMANUFACTURER'S SPECIFICATION'S SHOWING THE
 SEER OF THE SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]